D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 102 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Keypad Programming of P### Point Index 
D1255 
1.  Refer to Figure 1 on page 7 to access Keypad 
Programming and navigate to the POINT 
PARAMETERS 
option. The PT NUM 1 - ### 
option shows. 
2.  Enter the point number you wish to configure and 
press [ENT]. 
3.  The keypad shows the point number and the 
index number (for example, INDEX: 3). 
4.  Press [ENT]. An invisable editing cursor is 
enabled for point index number.  
5.  The [PREV] button acts as a [Backspace] key. 
Press [PREV] to delete the characters of the 
index number, and then enter the new index 
number. 
 
The keypad does not accept invalid index 
numbers. 
6.  Press [ENT] to save the changes. 
When the keypad reads PARAMETER SAVED, your 
selection has been configured. 
D1260
 
Press [ENT] to save the changes 
1.  Refer to Figure 2 on page 8 to access Keypad 
Programming and navigate to the Point 
Parameters 
option.  
2.  Press [ENTER]. The Point Num 1 – 247 (1 – 75 
for a D7412GV3) option shows. 
3.  Enter the point number you wish to configure and 
press [ENTER]. The keypad reads Point# Index
and then the currently configured index number 
(for example, Point (1) Index: 3). 
4.  Press the Edit softkey to change the point index. 
5.  The Backspace softkey allows you to erase 
characters. The Clear softkey allows you to clear 
the entire index number. Use the softkeys and 
the number buttons on the keypad to enter the 
new point index number. 
6.  Press the Save softkey to save the changes. 
When the keypad reads Parameter Saved, your 
selection has been configured. 
 
P### Area Assign 
Default: 
Selection: 
1 to 32 for D9412GV3 
1 to 8 for D7412GV3 
Select the area number to which the point is 
assigned. 
 
P### Debounce 
Default: 
Selection: 
1 to 15 
1 .300 
sec 
2 .600 
sec 
3 .900 
sec 
4 1.2 
sec 
5 1.5 
sec 
6 1.8 
sec 
7 2.1 
sec 
8 2.4 
sec 
9 2.7 
sec 
10 3.0 
sec 
11 3.3 
sec 
12 3.6 
sec 
13 3.9 
sec 
14 4.2 
sec 
15 4.5 
sec 
The debounce count is the number of times the 
control panel scans a point before generating an 
alarm. Scan cycles are 300 ms. 
For appropriate settings consult the manufacturer’s 
instructions for the device connected to this point. 
 
Use an entry of two or higher. Interior 
Follower points need a Debounce value 
of at least three. 
 
 
Door points assigned to D9210B modules 
need a Debounce value of at least four.