3.4 
COMMAND 7 and COMMAND 9 
These entries assign point indexes, associated relays 
that activate, and the text for the COMMAND 7 and 
COMMAND 9 keypad functions. 
CMD7 Point Index 
Default: 
31 
Selection:  0 to 31 
This entry selects one of the 31 P## Index codes that 
define how the control panel reacts when a 
COMMAND 7 is initiated. 
 
The point index code used for 
COMMAND 7 must not be used for any 
other points on the system. 
 
 
If the point index for COMMAND 7 has 
Fire points programmed as Yes, this 
causes access control doors to unlock if 
Fire Unlock is also programmed as Yes. 
Refer to the D9210B Program Entry 
Guide
 (P/N: 32207). 
 
CMD7 Relay 
Default: 
Selection: 
0 to 8 
This entry selects a relay (73 to 80 for the D9412GV3 
or 9 to 16 for the D7412GV3) when COMMAND 7 is 
initiated (refer to the 
P### Relay
 prompt on page 
103 for relay number association). 
 
 
 
COMMAND 7 does not activate the 
Summary Fire Alarm relay. 
CMD7 Point Text 
Default: 
COMMAND 7 
Selection:  Up to sixteen alphanumeric 
characters 
Enter alphabetic characters A to Z in capital letters 
Enter up to sixteen characters of text to describe the 
point. This point text appears at keypads (if the point 
is programmed as visible) and sent to the D6500 or 
D6600 when transmitting in Modem IIIa
2
 format (if it is 
a reporting point). 
 
CMD9 Point Index 
Default: 
31 
Selection:  0 to 31 
This entry selects one of the 31 P## Index codes that 
define how the control panel reacts when a 
COMMAND 9 is initiated. 
 
The point index code used for  
COMMAND 7 and COMMAND 9 must not 
be used for any other points on the 
system. 
 
 
If the point index for COMMAND 9 has 
Fire points programmed as Yes, this 
causes access control doors to unlock if 
Fire Unlock is also programmed as Yes. 
Refer to the D9210B Program Entry 
Guide
 (P/N: 32207). 
 
CMD9 Relay 
Default: 
Selection: 
0 to 8 
This entry selects a relay (73 to 80 on the D9412GV3 
or 9 to 16 on the D7412GV3) when COMMAND 9 is 
initiated (refer to the 
P### Relay
 prompt on page 103 
for relay number association). 
 
 
COMMAND 9 does not activate the 
Summary Fire Alarm relay. 
CMD9 Point Text 
Default: 
COMMAND 9 
Selection: 
Up to sixteen alphanumeric 
characters 
Enter alphabetic characters (A to Z) in capital letters 
Enter up to sixteen characters of text to describe the 
point. This point text is displayed at keypads (if the 
point is programmed as visible) and sent to the D6500 
or D6600 when transmitting in Modem IIIa
2
 format (if it 
is a reporting point).