D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL
EN | 140
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Table 38: Cross Point Ranges Within Groups
Cross Point
Group Point
Group Point
Range
1
1
to
8
2 9
to
16
3
17
to
24
4 25
to
32
5
33
to
40
6 41
to
48
7
49
to
56
8 57
to
64
9
65
to
72
10 73
to
80
11
81
to
88
12 89
to
96
13
97
to
104
14 105
to
112
15
113
to
120
16 121
to
127
17
129
to
136
18 137
to
144
19
145
to
152
20 153
to
160
21
161
to
168
22 169
to
176
23
177
to
184
24 185
to
192
25
193
to
200
26 201
to
208
27
209
to
216
28 217
to
224
29
225
to
232
30 233
to
240
31
241
to
247
Refer to Section 2.3 Routing on page 17 for
information about programming the destination (for
example, the central station) for Unverified Events.
An Unverified Event does not produce a
corresponding Restoral Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or trouble
conditions. Points programmed with point response D
(Delayed) eventually enter into an alarm condition if
the area is not disarmed in time.
information about programming the destination (for
example, the central station) for Unverified Events.
An Unverified Event does not produce a
corresponding Restoral Event.
The Cross Point function applies only to alarm
conditions. It does not apply to supervisory or trouble
conditions. Points programmed with point response D
(Delayed) eventually enter into an alarm condition if
the area is not disarmed in time.
Cross Point Time
Default:
20 sec
Selection:
5 sec to 255 sec
Select the amount of time (in seconds) that points
within a Cross Point Group are in alarm before a
Cross Point event is generated.
within a Cross Point Group are in alarm before a
Cross Point event is generated.
6.0 ACCESS
CONTROL
6.1 Door Profile
This programming category is used to:
Assign an area that also activates the D9210B
Assign a point to the door
Program the door state to change the time when
Assign an area that also activates the D9210B
Assign a point to the door
Program the door state to change the time when
the arm state changes
Allow for the Strike relay to activate upon a fire
alarm
Programming the Interlock point.
Door #
Default:
1
Selection:
1 to 8
Enter the number of the door you are programming.
The D9412GV3 supports up to eight
doors. The D7412GV3 supports two
doors.
doors. The D7412GV3 supports two
doors.
D# Entry Area #
Default:
0
Selection:
0 to 8
1 to 8
The area assigned to the door
controller to which the reader allows
access.
controller to which the reader allows
access.
0
Door controller does not function.
Assign an area to the door controller. This entry
allows the D9210B to be polled, activating
communication to the control panel. This is also the
area a user exits when initiating an REX.
allows the D9210B to be polled, activating
communication to the control panel. This is also the
area a user exits when initiating an REX.
The D# Entry Area # prompt for the
D9412GV3 is limited to the first 8 areas.
D9412GV3 is limited to the first 8 areas.