Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 6.0  ACCESS CONTROL 
EN | 145 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
D# REXShunt Only? 
Default: 
No 
Selection: 
Yes or No 
Yes 
Programmed shunt time activates 
so the door can be manually 
opened. 
No 
REX automatically activates the 
programmed strike and shunt time. 
Use this program item to disable the door strike, but 
activate the programmed D# Shunt Time upon a 
request to exit (REX) from an area. 
 
Use this parameter when a user can 
open a door manually without relying on 
a token or card to activate the strike 
(such as with a push bar). 
 
 
When REXShunt Only is Yes, REX 
Events are not logged, reported, or 
printed. 
 
6.3 Event 
Profile 
This programming category is used to determine if 
events are created for: 
  Access Granted and Access Denied 
  Door Requests 
  Door state changes due to manual (keypad) or 
automatic scheduled or armed state changes 
(skeds/hold open on disarm, normal on armed) 
operation. 
Door # 
Default: 
Selection: 
1 to 8 
Enter the door you plan to program. 
 
RTE Events require Access Granted to 
be programmed as Yes
 
D# Access Granted? 
Default: 
No 
Selection: 
Yes or No 
Yes 
Access Events from this door 
controller are sent to the control 
panel for processing. 
No 
Access Events from this door 
controller are not sent to the control 
panel for processing. 
This program item determines if Access Granted and 
Door Request Events are sent to the control panel for 
processing memory, printing, and remote reporting. 
 
A successful Access Event can be 
started by a(n): 
  Valid user ID 
  Valid door state changed at the 
keypad. 
  Automatically scheduled or armed 
state change that holds a door open 
  RTE or REX. 
D# No Entry? 
Default: 
No 
Selection: 
Yes or No 
Yes 
Access Denied Events from this 
door controller are sent to the 
control panel for processing. 
No 
Access Denied Events from this 
door controller are not sent to the 
control panel for processing. 
This program item determines if No Entry Events are 
sent to the control panel for processing memory, 
printing, and remote reporting. 
 
A No Entry Event can be caused by: 
  Invalid or unknown user ID, interlock 
or secured door, or incorrect authority 
level 
  RTE or REX at an interlocked door. 
  RTE or REX at a door in the secured 
mode.