Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 20 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
R# Backup Device
 
Default: 
No Device 
Selection: 
No Device, Phone 1..4, SDI ## 
Path 1..4 
Phone 1 
Phone 1 is this group’s backup 
destination if the primary 
destination fails. 
Phone 2 
Phone 2 is this group’s backup 
destination if the primary 
destination fails. 
Phone 3 
Phone 3 is this group’s backup 
destination if the primary 
destination fails. 
Phone 4 
Phone 4 is this group’s backup 
destination if the primary 
destination fails. 
SDI 88 Path 1 
Path 1 on SDI 88 is this group's 
backup destination if the primary 
destination fails. 
SDI 88 Path 2 
Path 2 on SDI 88 is this group's 
backup destination if the primary 
destination fails. 
SDI 88 Path 3 
Path 3 on SDI 88 is this group's 
backup destination if the primary 
destination fails. 
SDI 88 Path 4 
Path 4 on SDI 88 is this group's 
backup destination if the primary 
destination fails. 
SDI 92 Path 1 
Path 1 on SDI 92 is this group's 
backup destination if the primary 
destination fails. 
SDI 92 Path 2 
Path 2 on SDI 92 is this group's 
backup destination if the primary 
destination fails. 
SDI 92 Path 3 
Path 3 on SDI 92 is this group's 
backup destination if the primary 
destination fails. 
SDI 92 Path 4 
Path 4 on SDI 92 is this group's 
backup destination if the primary 
destination fails. 
 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, program a Backup 
Device
 
Select the communication device and the backup 
destination. The backup device is used when the 
primary device fails to reach the programmed 
destination. 
Refer to Section 5.5 
Programming Path Numbers 
and IP Addresses for Enhanced Communications on 
page on page 131 to enable enhanced communication 
paths. 
Keypad Programming of R# Backup Device 
D1255 
1.  Refer to Figure 1 on page 7 to access Keypad 
Programming and navigate to the 
ROUTE GRP 1 - 4 option. 
2.  At the ROUTE GRP 1 - 4 prompt, enter the route 
group number you wish to configure and press 
[ENT]. The keypad reads RT GRP 1 PRIMARY
and then the current configuration (for example, 
SDI 88 PATH 4). 
3.  Press [NEXT] to advance to the RT GRP 1 
BACKUP option. The Primary device cannot be 
set to No Device before setting the Backup 
Destination. 
4.  To change the configuration, press [ENT] when 
the current configuration shows, and then press 
[NEXT] or [PREV] to scroll through the options, as 
listed in R# Backup Device on page 20.  
5.  When the keypad reads the desired configuration 
option, press [ENT] to select it. 
When the keypad reads Parameter Saved, your 
selection has been configured. 
 
D1260 
1.  Refer to Figure 2 on page 8 to access Keypad 
Programming and navigate to the 
Route Group 1 - 4 option. 
2.  At the Route Group 1 - 4 prompt, enter the route 
group number you wish to configure and press 
[ENTER]. The keypad reads Rt Group 1 Primary
and then the current configuration (for example, 
SDI 88 PATH 4). 
3.  Press the Backup softkey. The keypad reads Rt 
Group 1 Primary, and then the current 
configuration (for example, SDI 88 PATH 4). The 
Primary device cannot be set to No Device before 
setting the Backup Destination. 
4.  To change the configuration, press the Edit 
softkey, and then press the Next or the Previous 
softkey to scroll through the options, as listed in 
R# Backup Device on page 20.  
5.  When the keypad reads the desired configuration 
option, press the Save softkey to select it. 
When the keypad reads Parameter Saved, your 
selection has been configured.