D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 22 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
User Reports 
Selecting Yes enables a report to be sent when the 
event occurs. 
Table 11: User Reports 
 
Report Selections 
Report 
Description 
R# Point 
Bypass 
Yes, No 
Point Bypass Event 
R# Forced 
Point 
Yes, No 
Forced Point Event 
R# Point 
Open 
Yes, No 
Point Opening 
Event 
R# Point 
Close 
Yes, No 
Point Closing Event 
R# Forced 
Arm 
Yes, No 
Point Force Armed 
R# Fail To 
Open 
Yes, No 
Fail to Open Event 
R# Fail To 
Close 
Yes, No 
Fail to Close Event 
R# Ext Clos 
Tm 
Yes, No 
Extend Close Time 
Event 
R# Opening 
Report 
Yes, No 
Opening Events 
R# Forced 
Close 
Yes, No 
Point Forced Close 
Event 
R# Closing 
Report 
Yes, No 
Closing Events 
R# FC 
Perimeter Inst 
Yes, No 
Forced Close 
Perimeter Instant 
Armed Event 
R# FC 
Perimeter 
Delay 
Yes, No 
Forced Close 
Perimeter Delay 
Armed Event 
R# Perimeter 
Inst Arm 
Yes, No 
Perimeter Instant 
Armed Event 
R# Perimeter 
Delay Arm 
Yes, No 
Perimeter Delay 
Armed Event 
R# Send User 
Text 
Yes, No 
User text 
 
 
Test Reports 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, enable Test Reports
Sending Test Reports 
Automatic:
 To send a single Test Report (R# Test 
Report
) automatically, enable Sked Function Code #9 
(Test Report) in the Skeds section of the program. 
Refer to Table 12. 
Manual: To send a single Test Report manually, enter 
[COMMAND][4][1] at the keypad. Refer to the Send 
Report
 prompt on page 62. 
To expand this Test Report to include any off-normal 
point condition or other off-normal system conditions, 
Expand Test Report (refer to page 14) must be 
programmed Yes. Refer to the footnotes with Table 13 
on page 24 for a list of event types that are included in 
an expanded test report. Additionally, the expanded 
test report includes Summary Fire Supervisory, 
Summary Fire Fault, Summary Controlled Point Fault, 
and Summary Point Device Fault conditions. 
The control panel can generate an Expanded Off- 
Normal Test Report by using Sked Function Code 28 
or a Non-Expanded Off-Normal Test Report using 
Sked Function Code 29. To generate this event, one 
or more points must be in an off-normal state at the 
time the Sked executes. Expanded Off-Normal Test 
Reports include the Off Normal Test Report Event as 
well as a panel-wide summary of off-normal point and 
system conditions. Non-Expanded Off-Normal Test 
Report Events are sent only when a point is in the off-
normal state but sends only the Off-Normal Test 
Report Event. 
Sending Status Reports 
Automatic:
 To send a Status Report automatically 
that includes the events shown in the footnotes in 
Table 12, enable Sked Function Code #10 in the 
Skeds section of the program. 
Manual: To send a Status Report manually that 
includes the events shown in the footnotes in Table 
12
, enter [COMMAND][4][2] at the keypad. Refer to 
the Send Report prompt on page 62. 
Sending off-normal conditions as a Status Report 
following a Test Report is required by some 
automation systems. Sending off-normal conditions as 
a Non-status Report that follows a Test Report is 
required for other automation systems. 
An off-normal condition is any point that is missing, 
trouble, supervisory, or in alarm. Also, points not 
cleared at the keypad report as off-normal.