Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 24 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
Table 13: Diagnostic Reports  
 
Report Selections 
Report 
Description 
R# SDI Dev Fail
1
 
Yes, No 
SDI device 
failure 
R# SDI Dev Restl 
Yes, No 
Restoral of SDI 
device failure 
R# Watchdog 
Rset 
Yes, No 
Watchdog 
Reset Event 
R# 
ParaChksmFail 
Yes, No 
Parameter 
checksum 
failure 
R# Reboot 
Yes, No 
Reboot Event 
R# Ph Line Fail
1
 
Yes, No 
Failure of phone 
line 
R# Ph Line Rstl 
Yes, No 
Restoral of 
phone line after 
failure 
R# AC Fail
1, 2
 
Yes, No 
Failure of AC 
power to control 
panel 
R# AC Restorl 
2
 
Yes, No 
Restoral of AC 
power to control 
panel after 
failure 
R# Batt Missing
1, 2
 
  Yes, No 
Battery Missing 
Detection Event 
R# Battery Low
1, 2
  Yes, No 
Low battery 
power 
R# Battery Rstl 
2
 
Yes, No 
Restoral of 
battery power to 
control panel 
after Missing or 
Low Event 
R# Rt Comm Fail
1, 
3
 
Yes, No 
Failure to send 
report to 
specific route 
R# Rt Comm Rstl 
Yes, No 
Restoral of 
communication 
to specific route 
after a failure 
 
 
Table 13: Diagnostic Reports (Continued) 
 
Report Selections 
Report 
Description 
R# Rt Comm Rstl 
Yes, No 
Restoral of 
communication 
to specific 
route after a 
failure 
R# Checksum Fail  Yes, No 
Checksum Fail 
Event 
R# Network Fail
4
 
Yes, No 
Failure of 
network 
R# Network Rest
4
 
Yes, No 
Restoral of 
network 
R# Network Cond
4
  Yes, No 
Condition of 
network 
1
  This event is included in the Expanded Test Report 
when an off-normal condition exists. 
2
  To meet UL 864 requirements for Central Station and 
Remote Station applications, enable AC FailBattery 
Missing
Low BatteryBattery Restoral, and AC 
Restoral
 reports. 
3
  This event covers Comm Fail Route Group and Comm 
Fail Phone. If enabled, both events are sent; if 
disabled, neither event is sent. 
This event is reserved for future use. 
 
 
 
Enable Rt Comm Fail and Rt Comm 
Restore in only one route group. 
Relay Reports 
Selecting Yes enables sending a report when the 
event occurs. 
Table 14: Relay Reports 
 
Report Selections 
Report 
Description 
R# Sensor 
Reset 
Yes, No 
Sensor Reset 
Event 
R# Relay Set 
Yes, No 
Relay Set Event 
R# Relay 
Reset 
Yes, No 
Relay Reset Event