D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 30 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
AC Tag Along is required for NFPA 
and UL 864 Commercial Fire systems. 
Be sure to program AC Fail/Restoral 
Report
 as No if AC Tag Along is 
programmed Yes
 
AC/Battery Buzz 
Default: 
No 
Selection: 
Yes or No 
Yes 
Initiates panel-wide trouble tone at 
all keypads. 
No 
Does not initiate panel-wide trouble 
tone at keypads 
Initiates a panel-wide trouble tone at keypads when 
AC fails or battery is low or missing. This program 
item does not prevent the SERVC AC FAIL or 
SERVC BATT LOW displays. 
 
To comply with NFPA standards and  
UL 864 requirements for Commercial Fire 
systems, program this item as Yes
 
 
If annunciating panel-wide troubles at a 
keypad with CC# Scope set to Panel 
Wide
 is undesirable, set CC# Trouble 
Tone
 to No. Refer to Section 2.9 Keypad 
(Command Center)
 on page 50 for 
keypad configurations. 
 
Bat Fail/Restoral Report 
Default: 
Yes 
Selection:  Yes or No 
Battery Failure and Restoral Reports are 
sent to the central station. 
Yes 
Modem 
Reports 
Missing or 
shorted 
Discharged 
below 12.1 
VDC 
BATTERY 
MISSING  
BATTERY LOW
 
 
No 
Battery Failure and Restoral Reports are not 
sent to the central station. 
 
 
To comply with NFPA standards and  
UL 864 requirements for Commercial Fire 
systems, program this item as Yes
2.5 Printer 
Parameters 
Up to three D9131A Parallel Printer Interface Modules 
can be connected to the D9412GV3’s (one printer for 
the D7412GV3’s) SDI bus. Each printer is identified by 
an address of 17, 18, or 19. Options are available for 
Routing Reports and area assignments. 
Printer Address 
Default: 
17 
Selection:  17, 18, or 19 (only 17 is available 
for the D7412GV3) 
Enter the printer address you are programming. 
P## Area Assign 
Default: 
Selection:  1 to 32 for D9412GV3 
1 to 8 for D7412GV3 
Assign an area to the printer programmed in Printer 
Address
P## Supervised 
Default: 
No 
Selection:  Yes or No 
Yes 
Only one printer can be installed for 
this P## SDI address. 
No 
More than one unsupervised printer 
can be installed using this P## SDI 
address and the same address DIP 
switch setting. 
Supervise this SDI address. Generate Trouble SDI ## 
Reports and local trouble annunciation if a problem 
occurs with this printer or the SDI bus. 
 
Unsupervised printers sharing the same 
address setting print the same text. 
 
 
Trouble SDI ## Reports are always 
reported as Area 1, Account 1 Events 
regardless of where the SDI device is 
assigned. 
 
 
When P## Supervised is set to Yes and 
all Printer Event Groups (such as P## 
Fire Events
P## Burglar Event, or P## 
Usr Chng Evt
) are set to No, the control 
panel does not generate Trouble SDI ## 
Reports for the printer if the D9131A 
becomes disconnected.