Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 35 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
RPS Phone # 
Default: 
Blank 
Selection:  Blank or up to 24 characters 
Blank 
Control panel does not dial a phone 
number for RPS. 
1 to 24 
characters 
Enter up to 24 characters to define 
dialing characteristics. 
This is the phone number the control panel dials to 
contact RPS. Refer to Section 2.6.1 on page 32 for 
instructions on configuring special phone number 
digits to detect dial-tone detect and to pause dialing. 
The control panel dials this number when any of the 
following events occur: 
  Log % Full threshold is achieved. 
 
If Log % Full is programmed with a 
value (1 to 99) and an RPS phone 
number or RPS IP address are 
programmed, the control panel attempts 
to communicate with Unattended RPS 
when the log threshold is reached.  
 
  The control panel is contacted by RPS and RPS 
Call Back is programmed Yes
  The user enters COMMAND 43 and selects the 
call RPS option from the menu. On the D1255: 
1.  Press [COMAND][4][3]. 
2.  Press [NEXT] until RPS via Phone? appears, 
then press [ENTER]. 
 
The control panel tries to contact RPS 
only once using this method. 
Refer to Section 5.4 SDI RPS Parameters on page 
126 for other connection methods. 
 
 
Refer to Phone #  in Section 2.1 Phone 
on page 12 for descriptions of special 
programming values for the RPS Phone 
number. 
 
Keypad Programming of RPS PHONE # 
D1255 
1.  Refer to Figure 1 on page 7 to access Keypad 
Programming and navigate to the RPS 
PARAMETERS
 option. Press [ENT]. The keypad 
shows the RPS PASSCODE option and the 
currently configured passcode. 
2.  Press [NEXT] to advance to the RPS PHONE 
NUMBER option.  
3.  The keypad shows the currently configured phone 
number. Press [ENT] to edit the phone number. 
4.  The [PREV] button acts as a [Backspace] key. 
Press [PREV] to delete the characters of the 
phone number, and then enter the new phone 
number. 
5.  Press [ENT] to save the phone number. 
When the keypad reads PARAMETER SAVED
your selection has been configured. 
 
D1260 
1.  Refer to Figure 2 on page 8 to access Keypad 
Programming and navigate to the RPS 
Parameters
 option. Press [ENTER]. The keypad 
shows the RPS Passcode and the currently 
configured passcode. 
2.  Press Phone Number softkey. 
3.  The keypad shows the currently configured phone 
number. 
4.  Press the Edit softkey to change the phone 
number. 
5.  The Pause and DT Detect (Dialtone Detect) 
softkeys enter special characters. The Backspace 
softkey allows you to erase characters. The Clear 
softkey allows you to clear the entire phone 
number. The [COMMAND] and [ENTER] keys 
allow you to enter an * or a #. Use the softkeys, 
the number buttons, and the [COMMAND] and 
[ENTER] keys on the keypad to enter the new 
phone number.  
6.  Press [ENT] to save the phone number. 
When the keypad reads Parameter Saved, your 
selection has been configured. 
RPS Modem Speed 
Default: 
1200 
Selection:  300, 1200, 2400 
Select the baud rate for RPS-to-control panel 
communication when using a PSTN connection.