2.7 Miscellaneous 
Duress Type 
Default: 
Selection:  0, 1, 2, or 3 
0  Do not send a duress event with any 
passcode. 
1  Increase the last digit by 1 to generate an 
alarm. For example, if the passcode is 6123, 
6124 activates a duress alarm. 
If the last digit of the passcode is 0, a duress 
alarm occurs when the user enters 1 as the 
last digit of the passcode. 
If the last digit of the passcode is 9, a duress 
alarm occurs when the user enters 0 as the 
last digit of the passcode. 
2  Increase the last digit by 2 to generate an 
alarm. For example, if the passcode is 6123, 
6125 activates a duress alarm. 
If the last digit of the passcode is 8, a duress 
alarm occurs when the user enters 0 as the 
last digit of the passcode. 
If the last digit of the passcode is 9, a duress 
alarm occurs when the user enters 1 as the 
last digit of the passcode. 
3  Send a Duress event when any Passcode with 
L# Send Duress set to Yes is entered. 
This program item determines when a passcode 
entry with L# Send Duress authority should produce 
a duress alarm. 
 
Duress is enabled in Area Parameters by 
setting A# Duress Enable to Yes
 
 
The duress alarm activates when a user 
enters the duress passcode followed by 
the termination keys ([ESC] or [ENT]). 
For SIA CP-01 Compliance 
Duress Type
 must be set to 3
 
Cancel Report 
Default: 
No 
Selection:  Yes or No 
Yes 
Send Cancel and Fire Cancel 
Reports according to routing. 
No 
Do not send Cancel and Fire Cancel 
Reports. 
A Cancel and Fire Cancel Report is created when a 
passcode is entered to silence an Alarm Bell or a Fire 
Bell before the bell time expires. 
For SIA CP-01 Compliance 
This prompt must be set to Yes
Call for Service Text 
Default: 
Refer to the program record sheet 
Selection:  Twenty alphanumeric characters 
Enter the text to display on a D1260 series keypad 
when the control panel is out of service. 
 
2.8 Area 
Parameters 
This programming module contains three 
programming categories: Area Parameters, Bell 
Parameters, and Open/Close Options. 
2.8.1 Area 
Parameters 
Enter the area number you are programming. 
Area# Area On 
Default: 
Yes (Area 1 only) 
Selection:  Yes or No 
Yes Enable 
area. 
No Disable 
area. 
Use this program item to enable or disable the area 
specified. 
Refer to Keypad Programming of Area # On and 
Area# Account Number
 on page 37.