D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 39 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
When the detector senses smoke or fire, the area’s 
sensor reset relay interrupts power to points 
connected to it for the time in Verify Time. 
When power restores to the points, the 60-sec 
confirmation window starts. If any detector, reset 
during the verification time, experiences another alarm 
during the confirmation window, an alarm occurs. If no 
activity occurs during this period, no alarm occurs and 
the verification window ends. If a Verification point 
senses another alarm after the window ends, a new 
verification cycle begins. Refer to Table 21  on page 
39 for an example of Verify Time.  
To meet UL 864 requirements, set A# 
Verify Time
 to 60 sec. 
 
 
Table 21: Verify Time 
 
 
Verification 
Point Activation 
Verify Time/Reset 
Sensors
 
Power removed, 
ignore activity 
60 sec Confirmation 
Generate alarm if 
additional activity 
received. 
Restart Alarm 
Verification Cycle if 
an Alarm Verification 
point activates. 
Example: Total 
Cycle time 80 sec 
 
20 sec 
60 sec 
 
 
 
A# Duress Enable 
Default: 
No 
Selection:  Yes or No 
Yes 
Enable Duress alarm for this area. 
No 
Disable Duress alarm for this area. 
Refer to Duress Type in Section 2.7 Miscellaneous  
on page 36 for an explanation of duress. 
 
For SIA CP-01 Compliance: 
A# Duress Enable
 must be set to Yes
 
The passcode you normally use for 
duress is not valid in an area with A# 
Duress Enable
 set to No
If a passcode with the appropriate  
L# Disarm authority is used to duress 
disarm an area with A# Duress Enable 
set to No, NO AUTHORITY appears in 
the display. Also, if the keypad display is 
moved to an area with A# Duress 
Enable
 set to No using 
[COMMAND][5][0], a valid duress disarm 
passcode does not send a duress report.