Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 43 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
A# Single Ring 
Default: 
No 
Selection:  Yes or No 
Yes 
One bell output per arming period. 
After one alarm, alarms on any Non-
fire points in the same area cannot 
restart the bell until the armed state 
changes. An alarm on a different 
point in same area restarts bell 
output. 
No 
Restart bell output with each alarm 
event. 
Determines if an alarm from a non-fire point can 
restart the alarm bell time with each Alarm Event, or 
only start alarm output once per arming period. 
This does not silence the keypad alarm bell tone, or 
prevent any reports. This feature does not affect Fire 
points. Fire points restart bell time with each new 
alarm. 
 
If an alarm occurs on a 24-hour point 
while the area is disarmed, arming that 
area with a key switch does not clear 
the A# Single Ring flag. 
 
 
Silencing the bell resets A# Single 
Ring
A# Bell Test 
Default: 
No 
Selection:  Yes or No 
Yes 
Start Bell Test. 
No 
Do not start Bell Test. 
Provides alarm output from the relay programmed at 
A# Alarm Bell after the Closing Report is confirmed 
or the exit delay time expires. 
Bell Test After Confirmation 
In areas that send Opening and Closing Reports, the 
Bell Test occurs after the control panel sends the 
Closing Report and receives an acknowledgment 
from the central station receiver. For proper operation 
of the Bell Test after closing confirmation, the 
following rules apply: 
  The control panel must send Opening and 
Closing Reports to the central station. 
  Do not use restricted openings and closings or 
Opening and Closing Windows. 
Area Armed Confirmation 
In areas that do not report opening and closing 
activity, the alarm bell relay output for this area 
activates for 2 sec after exit time expires. 
Multiple Bell Tests occur: When more 
than one area is armed at the same time 
(such as using the ARM ALL AREAS? 
function), the bell rings for 2 sec with a 
2 sec pause between each bell activation 
if all areas have the same exit delay time 
programmed. Otherwise, the Bell Test 
occurs as each area arms and it 
completes its exit delay time. 
When areas arm simultaneously and 
report to the central station, the Bell 
Test occurs as the central station 
receiver confirms each area. 
2.8.4 Open/Close 
Options 
Programming determines if Opening, All Normal 
Closing, and Force Arm/Bypass Closing Events are 
sent to the remote central station. Without remote 
reports, all control panel and area arming (Closing 
Events) and disarming (Opening Events) default to 
local events. 
Use this programming category to determine which 
opening and closing supervision characteristics are 
needed. 
There are three ways to generate reports from the 
control panel. You can generate reports by account, 
by area, or a combination of both. 
Opening and Closing Events are sent 
only by users with the proper authority 
settings.