Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 51 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
CC# Supervised 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
Yes 
Only one keypad can be installed for this 
CC SDI address. 
No 
More than one keypad can be installed 
using this CC SDI address with the same 
address DIP switch setting. 
Supervise this SDI address and generate Trouble 
SDI Reports and local trouble annunciation if a 
problem occurs with this keypad or the SDI bus. 
 
 
To meet UL 864 requirements, set CC# 
Supervised
 to Yes for the fire 
annunciation keypad. 
 
 
Keypads that share the same address 
setting display the same text and emit the 
same tones, regardless of which keypad’s 
keys are pressed. 
Trouble SDI # Reports are always 
reported as Area 1, Account 1 Events 
regardless of the area the SDI device is 
assigned. 
 
 
When this prompt is Yes, you cannot 
have duplicate DIP switch settings. 
CC# Enhanced Command Center 
Default: 
No 
Selection: 
Yes or No 
Yes 
This keypad is a D1260 Series 
Keypad. 
No 
This keypad is not a D1260 Series 
Keypad. 
When a D1260 Series Keypad is installed at this 
keypad address, this item must be set to Yes.  
Keypad Programming of CC# EnhancCMDCTR
  
D1255 
1.  Refer to Figure 1 on page 7 to access Keypad 
Programming and navigate to the COMMAND 
CENTER 
option.  
2.  Press [ENT]. The CC NUM 1 – 16 option shows. 
3.  Enter the keypad number you wish to configure 
and press [ENT]. The keypad reads CC# 
SCOPE
, and then the current configuration (for 
example, PANEL WIDE). 
4.  Press [NEXT]. The current keypad type shows 
(for example, CC - 1 TYPE ENHANCED: YES). 
5.  Press [ENT] to change the keypad’s type. 
6.  Press [NEXT] or [PREV] to toggle to No to 
indicate that the D1255 is not an enhanced 
keypad, and then press [ENT] to save the 
changes.  
When the keypad reads PARAMETER SAVED, your 
selection has been configured. 
D1260 
1.  Refer to Figure 2 on page 8 to access Keypad 
Programming and navigate to the Command 
Center 
option.  
2.  Press [ENTER]. The CC Num 1 – 16 option 
shows. 
3.  Enter the keypad number you wish to configure 
and press [ENTER]. The keypad reads CC# 
Scope
, and then the current configuration (for 
example, Panel Wide). 
4.  Press the Type softkey. The current keypad type 
shows (for example, CC (1) Type Enhanced: 
Yes). 
5.  Press the Edit softkey to change the keypad’s 
type. 
6.  Press the Yes or No softkey, and then press the 
Save softkey to save the changes. 
When the keypad reads Parameter Saved, your 
selection has been configured. 
 
Reboot the system to enable a D1260 
Series Keypad.  
To reboot the system, close and open the 
reset switch, labeled “S1 RESET,” 
located in the upper right corner of the 
control panel. 
 
CC# Area Assign 
Default: 
Selection:  1 to 32 on D9412GV3  
1 to 8 on D7412GV3 
Enter the area number where you are installing this 
keypad or keypads with this address and the same 
DIP switch settings.