Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 56 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
CC# Scroll Lock 
Default: 
No  
Selection: 
Yes or No 
Yes 
Prevents the idle system status text 
from scrolling automatically. 
Requires user intervention to 
advance. 
No 
Allows the idle system status text to 
scroll automatically without user 
intervention 
Use this parameter to enable a special non-scrolling 
option for the idle system status display text on a 
keypad. This keypad mode requires the user to press 
the PREV or NEXT key on the keypad to unlock the 
display and begin scrolling through the system status 
displays. 
CC# Menu Key Lock 
Default: 
No  
Selection: 
Yes or No 
Yes 
If set to Yes, the user is prompted to 
enter a passcode after pressing the 
Menu key on the keypad. The items 
programmed in the Menu List for this 
specific keypad are filtered by the 
user’s authority level. Only those 
items in the menu list for which the 
user has authority appear. 
No 
If set to No, when the user presses 
the Menu key, all items that are 
programmed in the Menu List for the 
Command Center Address (Keypad 
Address) appear, regardless of the 
user’s authority level. 
Determines if the Menu Key, when pressed, requires 
a passcode to access the functions. 
 
If this parameter is set to Yes, users must 
enter a passcode after pressing the Menu 
key. When the passcode is validated, 
only those functions for which the user 
has authority appear in the list. If a 
function in the Menu List is passcode 
protected (refer to Keypad Functions in 
Section 2.11.2 User Interface on page) 
the user does not need to enter the 
passcode again.  
 
CC# Abort Display 
Default: 
Yes 
Selection:  Yes or No 
Yes 
This keypad shows the Alarm 
Aborted message for all aborted 
alarms within its scope. 
No This 
keypad 
does 
not show the 
Alarm Aborted message for all 
aborted alarms within its scope. 
This parameter enables or disables the ALARM NOT 
SENT message when an alarm is aborted before 
transmission occurs. 
For SIA CP-01 Compliance 
CC# Abort Display
 can be set to Yes or No
CC# Cancel Display 
Default: 
Yes 
Selection:  Yes or No 
Yes 
This keypad shows the Cancel 
Report Sent message for all canceled 
alarms within its scope. 
No This 
keypad 
does 
not show the 
Cancel Report Sent message for all 
canceled alarms within its scope. 
This parameter enables or disables the CANCEL 
REPORT SENT display message when an alarm is 
canceled after transmission occurs. To show this 
message, Cancel Report must be set to Yes. Refer to 
Cancel Report on page 36. 
For SIA CP-01 Compliance 
CC# Cancel Display
 can be set to Yes or No
 
2.9.2 Area 
Text 
Use this programming category to create custom Idle 
Text displays for the keypads. 
 
Each display can be programmed with up 
to sixteen alphanumeric characters, 
including: A to Z, 0 to 9,  ?,  &, @,  -,  *,  
+,  $,  #,  _,  /. 
Characters not listed are invalid and 
cannot be used for text.