D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 69 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
L## View Memory 
Default: 
Refer to the program record sheet 
Selection:  - or E 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
View Event 
Memory 
[COMMAND][4][0] 
View all memory events that occurred since the last 
time the system was armed for all areas within the 
scope of the keypad in this area. 
L## View Point Status 
Default: 
Refer to the program record sheet 
Selection:  - or E 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
10 
View Point Status  (Menu function 
only) 
View the current status of all points in the area to 
which this keypad is assigned. 
L## Walk Test 
Default: 
Refer to the program record sheet 
Selection: 
- or E 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
11 Walk 
Test 
[COMMAND][4][4] 
Walk Test all Interior or Perimeter Controlled points in 
the area to which this keypad is assigned. 
The following features come with the Walk Test 
Mode: 
  Battery powered control panel only. A Battery 
Test runs during the whole test to ensure that the 
battery capacity is capable of supporting the full 
load of the control panel if AC fails. 
This test includes 2-sec Bell Test when the 
Walk Test starts. 
The test ends when all points are tested or 
the test times out after 20 min of no activity. 
  Local alarm annunciation and event printing; no 
reports are sent to the central station receiver. 
  D1255 Keypad displays a sequential count, and 
text after each point is activated and restored. 
  The keypad displays ALL PTS TESTED and an 
All Points Tested Event is sent to the central 
station receiver (if programmed) when the last 
point is tested. 
  If enabled in Routing, Walk Start and Walk End 
Reports are sent to the central station receiver at 
the beginning and end of the test. 
 
To Walk Test a Door point connected to a 
D9210B Access Interface Module, open 
the door without activating the door 
sequence or allowing it to time out past 
the extended shunt time. 
L## Fire Test 
Default: 
Refer to the program record sheet 
Selection:  - or E 
 
Function 
No. 
Function Name 
Alternate 
Keystroke 
12 Fire 
Test 
[COMMAND][5][8] 
Fire Walk Test all 24-hour points in the area where 
this keypad is assigned. 
One person can perform a Fire Walk Test without 
assistance. The following features come with the Fire 
Test Mode: 
  Battery powered control panel only. A Battery 
Test runs during the whole test to ensure that the 
battery capacity is capable of supporting the full 
load of the control panel if AC fails. 
This test includes a 2-sec Bell Test (Fire Bell 
relay) for each Fire point that is tested. 
The test ends when all points are tested or 
the test times out after 20 min of no activity. 
  Local alarm annunciation and event printing; no 
reports are sent to the central station receiver. 
  Automatic smoke detectors reset for all Fire 
points programmed with P## Resettable as Yes
  D1255 Keypad displays a sequential count and 
the text for the point after each point is activated 
and restored. 
  If enabled in Routing, Walk Start and Walk End 
Reports are sent to the central station receiver at 
the beginning and end of the test. 
 
A# Verify Time for Fire points that is 
programmed with Yes for P## Alarm 
Verify
 is ignored during the Fire Walk 
Test.