Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 79 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Relay functions that resume the proper state 
within one minute: 
Alarm Bell 
Perimeter Fault 
Summary Fire 
Summary Trouble 
Area Armed 
Reset Sensors 
Fire Bell 
AC Fail 
Summary Alarm 
Phone Fail 
Silent Alarm 
Summary SupBurg 
Area Fault 
Battery Trouble 
Summary Fire Trouble  Communications Fail 
Watch Mode 
Summary SupFire 
Relay functions that must be reset manually 
with Change Relay function (COMMAND 54): 
Fail To Close 
Force Armed 
Duress 
Log % Full 
 
2.12.1 Area Relays 
Each area can be assigned a unique relay number 
for each of the events listed in this section. 
A# Alarm Bell 
Default: 
Selection: 
0, 1 to 128 for D9412GV3 (1 to 64 
for D7412GV3), A, B, or C 
This voltage output relay activates and provides  
12 VDC output when a Non-fire point (P## Fire is 
No) assigned to this area activates an alarm. 
 
A# Burg Time and A# Burg Pattern 
must be programmed in Area or Bell 
Parameters. This relay activates 
according to the bell pattern and remains 
active until the bell time expires or a valid 
passcode is entered. P## Silent Bell 
must be No for the bell to ring upon 
alarm. 
For SIA CP-01 Compliance: 
Do not set A# Alarm Bell to 0. This feature is 
required for SIA CP-01 compliance. 
A# Fire Bell 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
This voltage output relay activates and provides  
12 VDC output when a Fire point (P## Fire is Yes
assigned to this area activates an alarm. 
 
Fire Time and Fire Pattern must be 
programmed in Bell Parameters. This 
relay activates according to the bell 
pattern and remains active until the bell 
time expires. P## Silent Bell must be No 
in order for the bell to ring upon alarm. 
 
 
Although Relay C is a valid entry for A# 
Fire Bell
, do not program Relay C for this 
entry. Use Relay A for the A# Fire Bell
 
To meet UL 864 requirements, set A# 
Fire Bell
 to a value other than 0. 
 
A# Reset Sensors 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3,A, B, or C 
Unlike the default relay for Alarm Bell and Fire Bell, 
this voltage-output relay (Relay C) de-activates for 
5 sec when the Reset Sensors? function is activated 
from the keypad or during a Fire Walk Test. 
 
The Reset Sensors time converts from 
the  
5 sec default time to the time 
programmed in A# Verify Time (Section 
2.8 Area Parameters 
on page 5) when a 
point programmed for P## Alarm Verify 
(Section 3.1 Point Index on page 87) 
enters an alarm condition.