Bosch d9412gv3 User Manual

Page of 154
D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 81 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
A# Duress Relay 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when a Duress alarm is generated from a 
keypad assigned to the specified area. 
 
Burg Time needs a bell period 
programmed and A# Duress Enable 
must be Yes. This relay activates when 
the Burg Bell starts and deactivates when 
the Burg Bell time ends. The Burg Bell 
pattern has no effect on this relay 
function. 
A# Perimeter Fault 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when a Controlled Perimeter point (P## 
Type 1
) assigned to the specified area is faulted,  
regardless of the armed state of the area. This relay 
provides a steady output until all Perimeter points in 
the area return to normal. 
 
This relay does not activate on interior 
faults. To detect all area point faults, 
program all points as Perimeter points in 
the area where this relay is assigned. 
A# Silent Alarm 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
This relay activates when a point assigned to the 
specified area and programmed for P## Silent Bell 
goes into alarm. 
 
2.12.2 Panel-Wide Relays 
The following eleven relay options activate when they 
occur anywhere in the control panel. They are not 
restricted by area boundaries. 
AC Failure 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when the control panel responds to an AC 
power failure as programmed in AC Fail Time in 
Section 2.4 Power Supervision on page 29. This 
relay automatically resets when AC power restores. 
 
Use this relay to create audible 
annunciation. Enable the keypad’s 
trouble sounders for all applications 
except commercial fire systems. 
Battery Trouble 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when battery voltage falls below 85% of 
capacity (12.1 VDC) for a fully charged (13.8 VDC) 
battery, or when the battery is in a missing condition. 
This relay automatically resets when battery power 
restores. 
 
Use this relay to create audible 
annunciation. Enable the keypad’s 
trouble sounders for all applications 
except commercial fire systems. 
Phone Fail 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when a telephone line failure occurs. A time 
must be entered in Ph Supv Time (refer to Section 
2.2 Phone Parameters 
on page 14) for this relay to 
activate. This relay resets automatically when restoral 
of the phone line(s) occurs.