D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 82 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
Comm Fail 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when a control panel cannot communicate 
a report after making ten attempts to each routing 
destination. At the same time, COMM FAIL RG  
displays at the keypad. This relay automatically 
resets when a report is sent successfully. 
 
Use this relay to report primary digital 
report failure to an alternate 
communication device. 
Log % Full 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Enter the number of the relay that activates when the 
log reaches the programmed percentage of its 
capacity as programmed in the Log % Full prompt 
under PANEL WIDE PARAMETERS >RPS 
Parameters. This relay provides a steady output until 
a Get Log and Set Pointer is executed from the 
remote programming software (RPS). 
Summary Fire 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Enter the number of the relay that activates when any 
Fire point in the system (P## Type 0P## Fire Yes
enters into alarm. This relay provides a steady output 
until all Fire points in the system return to normal. 
Refer to Fire Summary Sustain on page 137 for 
details on alternate operation. 
Summary Alarm 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Enter the number of the relay that activates when a 
Non-fire point enters into alarm. This relay provides a 
steady output until the alarm is acknowledged by a 
valid passcode, then cleared from alarm memory with 
an acknowledgment at the keypad. 
 
This relay does not activate for silent and 
invisible alarms. 
Summary Fire Trouble 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when any Fire point in the control panel is 
in trouble, or if a Fire Supervision point is missing. 
This relay provides a steady output until all Fire 
points restore to a normal condition.  
Summary SupFire 
Default: 
Selection: 
0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when any Fire Supervisory point in the 
control panel is in a supervisory condition (off-
normal). This relay provides a steady output until all 
Fire Supervisory points are restored to a normal 
condition. 
Summary Trouble 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when any Non-fire point in the control panel 
is in a trouble condition. This relay provides a steady 
output until the user at the keypad acknowledges the 
trouble. 
Summary SupBurg 
Default: 
Selection:  0, 1 to 128 for D9412GV3, 1 to 64 
for D7412GV3, A, B, or C 
Activates when any Non-fire Supervisory point in the 
control panel is in a supervisory condition, or if a 
Supervisory Burg point is missing. This relay provides 
a steady output until the user at the keypad 
acknowledges the condition.  
 
2.1 
Passcode or Token Worksheet 
These programming items assign: 
  a passcode to user groups 001 to 249, 
  areas by authority level, and 
  a User Group Window.