D9412GV3/D7412GV3 | Program Entry Guide | 2.0  Panel and Area Wide Parameters 
EN | 85 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
User ### 
Default: 
001 
Selection: 
000 or 001 to 249 (001 to 099 for 
the D7412GV3) 
Enter the User number you are programming. 
 
 
User 000 is the Service Authority Level 
(Level 15). You cannot change the 
programming for user 000. 
Only the Service Authority Level (User 
000) can delete User 000. When a user 
other than User 000 tries to delete the 
passcode for User 000, the keypad 
displays NOT IN USE. 
User 000 cannot be added or changed 
at the keypad whether it exists or not. 
 
U### Passcode 
Default: 
Refer to the program record sheet 
Selection:  Three to six digits ( 0 to 9) 
Enter three to six digits to enable a passcode for the 
master user in this group. 
 
 
To meet UL 864 requirements, enter at 
least one Passcode. 
 
 
User I.D.000 is the reserved user for 
service personnel. The default service 
passcode is 123. 
The programmer does not allow you to 
enter any passcode number that might 
conflict with a duress passcode. The 
programmer reserves the passcode 
number plus 1, duress passcode number 
plus 2, passcode-number minus 1, and 
passcode number minus 2.  
For example, when a passcode of 
654321 is entered, 654322, 654323, 
654320, and 654329 are reserved and 
are not available to other users. 
 
 
The authority to silence a bell is granted 
to all passcodes regardless of their 
authority level assignments. A user 
passcode can silence a Fire or Burg bell 
as long as any authority level is assigned 
to the area where the bell can be 
silenced. 
 
U### User Group 
Default: 
Selection: 
0, 1 to 8 
Create a group of up to 249 users (99 for the 
D7412GV3) whose combinations can be enabled and 
disabled using an automatic user window. This is the 
number entered into the W# User Group for any 
active W# User Window. Multiple windows can be 
programmed for one user group (up to eight) within 
one 24-hour period. For example, if User Group 1 
has a window running from 8:00 AM (start time) to 
4:00 PM (stop time), the users for that group can use 
their passcodes only between that time. Between 
4:00 PM that day and 8:00 AM the next day, the 
users cannot use their passcodes. 
 
To enable this user’s passcode at all 
times, leave U### User Group 0. 
User Group Window times cannot be changed from 
the keypad. When a window is assigned to a user 
group, the users in that group rely on the window to 
be active (within the start and stop times) for their 
passcodes to function. The only way to disable the 
window is by reprogramming the control panel from 
the remote programming software (RPS). 
U### Area 1 [through Area #] Auth 
Default: 
Refer to the program record sheet 
Selection:  0 to 14  
Assign an authority level to the user for this area. 
A setting of 0 means the user has no authority in this 
area. 
 
To meet UL 864 requirements, assign a 
valid authority level to the Passcode to 
silence bells.