D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 91 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
3.2 Point 
Responses 
3.2.1  Applications for Point Responses 9, 
D, and E: 
Combine Point Responses 9, D, and E with 
Perimeter point types to create more flexible 24-hour 
protection. Unlike 24-hour points, a faulted Perimeter 
point with a Point Response of D and E displays at 
the keypad when arming. Like a 24-hour point, a 
point programmed this way can generate alarms 
whether the area is armed or disarmed. 
Combining Point Response 9 with the Local While 
Disarmed feature provides off-site reporting when the 
area is armed, but only local alarm annunciation 
when the area is disarmed. 
Combining Point Response 9 with the Local While 
Armed feature provides off-site reporting when the 
area is disarmed, but only local alarm annunciation 
when the area is armed. 
Point Response E: Use this setting for Zonex or 
ASIC motion detectors. The control panel can report 
troubles while Master Armed. 
Point Response F: Does not sound at local keypads 
but activates a relay when P## Relay Response 
Type
 
is set to 1 and annunciates a fault at the 
keypadsTo annunciate the off-normal state at a 
keypad, program P## Display as Device as Yes or 
optionally set P## BuzzOn Fault as 1 or 2. This point 
response does not generate alarms nor does it 
activate the Alarm Bell. 
Point Response 8, 9, A, B, and C: These point 
responses provide supervisory (24-hour) reporting. 
3.2.2  Characteristics of a Fire Point: 
Reporting:
 When a group of events occurs, the 
control panel routes and prints out Fire Reports first. 
Visual Annunciation: FIRE TROUBLES continues 
to scroll until the trouble clears. When acknowledged, 
a FIRE TROUBLE scroll notifies the end user that a 
Fire point, or group of Fire points, is still in trouble. 
Panel-Wide Relays, Summary Fire, and Summary 
Fire Trouble
 activate if a relay is assigned when any 
Fire point enters into alarm or is in trouble. 
Audible Annunciation: A Fire point activates the  
A# Fire Bell relay programmed in Relay Parameters. 
The amount of time and the pattern of the relay 
activation is programmed by area in Bell 
Parameters
A# Fire Time, and A# Fire Pattern
Supervisory: A Fire point can send a Fire 
Supervisory Report and activate the Summary Fire 
Sup and Summary Fire Trouble, Panel-Wide 
Relays with a P## Response of 8-9-A-B-C. 
Alarm Verification: A Fire point can delay an alarm 
by the length of time programmed in A# Verify Time 
in the Area Parameters. Combined with A# 
Resettable
, a Fire point also resets the electrical 
circuit for the amount of time programmed. 
Reset Sensor: A fire device that requires resetting 
can be manually reset using the reset sensor relay 
for the area to which it is assigned. 
Fire Walk: Use the Fire Walk function to test Fire 
points in the system. The Fire Walk Test 
automatically resets each point for 5 sec when the 
point is activated, and rings the Fire Bell for 2 sec. 
 
To provide an audible tone for a restored 
Fire Supervisory point, use P## Relay 
Response Type
 set to 1 and connect the 
corresponding relay to a visual 
annunciator.