D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 96 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
P## Watch Point 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
Yes 
Activates Watch Mode responses if 
the point is faulted while the control 
panel is in Watch Mode. 
No 
Does not activate Watch Mode 
responses for this point. 
Use this option to allow a Controlled point to generate 
a watch tone while the area is disarmed and not 
faulted to a trouble or alarm condition. 
P## Relay Response Type 
Default: 
Refer to the program record sheet 
Selection:  0 to 2 
Point state does not affect the 
operation of the corresponding relay. 
Relay Follows Point: The relay 
corresponding with this point 
activates when the point is faulted to 
any off-normal condition, even if the 
point is bypassed. The relay 
automatically resets when the point 
returns to normal. 
Relay Latches: The relay 
corresponding with this point latches 
when the point enters into an alarm 
condition. This relay provides a 
steady output until the alarm is 
acknowledged by a valid passcode, 
then cleared from alarm memory with 
an acknowledgment from the keypad. 
Use this option to cause a relay (1 to 127 for 
D9412GV3; 1 to 64 for D7412GV3) to respond when 
a corresponding point with the same number (1 to 
127) is faulted. This requires connecting D8129 
OctoRelays to Zonex Bus 1 and Zonex Bus 2 
(D9412GV3 only). Refer to the address settings on 
the back of the D9412GV3/D7412GV3 Program 
Record Sheet 
(P/N: F01U170809). 
 
Point 128 is reserved for use other than 
an actual point. Only the first 127 points 
can have an associated relay. Relays are 
not available for Points 129 to 247. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Do not use the Change Relays? function 
to toggle relays reserved for special 
functions. Special function relays are 
Area and Panel Wide Relay functions as 
well as relays assigned to CC## Enter 
Key Relay and P## Relay Response 
Type
 
P## Display as Device 
Default: 
No 
Selection:  Yes or No 
Yes 
Display CHECK DEVICE when this 
point is off-normal. 
No 
Do not display CHECK DEVICE 
when this point is off-normal. 
Use P## Display as Device to cause the keypad to 
display CHECK DEVICE when a point is off-normal or 
is acknowledged after going into alarm. 
 
Use this function for devices with a dry 
contact output that faults a point when 
the device is in a trouble condition. 
P## Local While Disarmed 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
Yes 
Suppress Alarm, Trouble and 
Restoral* Reports from this point 
while the area to which it is assigned 
is disarmed. 
No 
Send event reports occurring from 
this point while the area is disarmed. 
*  Transmission of Restoral Reports continues if the alarm, 
trouble, or bypass (by Sked, RPS, or Swinger bypass) 
condition occurred when the area disarmed, and the point 
restored. 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, set this parameter to No
Use this option to allow a Controlled point (P## Type 
1, 2, 3
), to report Alarms, Troubles, and Restoral 
Reports only when the area is armed. This prompt 
does not affect local annunciation.