D9412GV3/D7412GV3 | Program Entry Guide | 3.0  Points 
EN | 97 
 
 
Bosch Security Systems, Inc. | 10/11 | F01U170807-02 
 
 
 
Local While Disarmed suppresses all 
reports from 24-hour points. Do not use 
P## Type 0 for this prompt. Remember 
that this option works only for Disarmed 
points, and a Type 0 is a 24-hour Always 
Armed point. Instead, choose any type 
other than 0, and use a point response 
that reports an alarm, whether or not the 
point is armed. For instance, P## Type 1 
and P## Response 9 reports an alarm on 
an open or a short (I) whether the area is 
armed or not. 
Local While Disarmed affects Keyswitch 
points. This prompt suppresses 
keyswitch (troubles and restorals) and 
D279 (alarms, troubles, and restorals). 
Do not use this parameter for these 
applications. 
P## Local While Armed 
Default: 
No 
Selection:  Yes or No 
Yes 
Suppress Alarm, Trouble and 
Restoral* Reports from this point 
while the area to which it is assigned 
is armed. 
No 
Report events occurring from this 
point while the area is armed. 
*
  Transmission of Restoral Reports continues if the alarm, 
trouble, or bypass (by Sked, RPS, or Swinger bypass) 
condition occurred when the area disarmed, and the 
point restored. 
 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, set this parameter to No
 
Allows a controlled point (P## Type 1, 2, 3), to report 
Alarms, Troubles, and Restoral Reports only when 
the area is disarmed. This prompt does not affect 
local annunciation.  
 
 
Local While Armed suppresses all reports 
from 24-hour points. Do not use P## Type 
0 for this prompt. This setting works only 
for disarmed points. Type 0 is a 24-hour, 
always armed point. Choose any Type 
other than 0, and use a point response 
that reports an alarm whether or not the 
point is armed. For instance, P## Type 1 
and P## Response 9 reports an alarm on 
a trouble or a short whether or not the 
area is disarmed. 
Local While Armed affects Keyswitch 
Points. This prompt suppresses 
keyswitch (alarms, troubles, and 
restorals) and D279 (opening, closing, 
troubles, and restorals). Do not use this 
parameter for controlled points that arm 
or disarm. 
P## Disable Restorals 
Default: 
No 
Selection:  Yes or No 
Yes 
Enable Restoral Reports from this 
point. 
No 
Disable Restoral Reports from this 
point. 
 
To meet UL 864 requirements for 
Central Station and Remote Station 
applications, set this parameter to No
 
Use this option to disable any Restoral Reports from 
this point after it returns to normal from an alarm or 
trouble condition. 
P## Force Arm Returnable 
Default: 
No 
Selection:  Yes or No 
Yes 
This point automatically returns to the 
system when it restores to normal. 
No 
This point stays out of the system 
until the area is disarmed. 
Use this option to allow points that were force armed 
out of the area to return back to the armed state when 
they become normal again without having to disarm 
the system. 
 
Use on loading dock doors, that must 
remain open until loading is completed. 
After the loading dock door is closed, the 
point detects any subsequent opening 
and reports an alarm.