PowerLogic ION7550 / ION7650 Installation Guide
© 2007 Schneider Electric.  All rights reserved.
 23
1
A baud rate of 300 bps is only intended for paging applications.
2
Serial number = PA-0302B222-01, Unit ID = 2222
3
Default IP ADDRESS = 172.16.xxx.xxx, where the last two bytes (decimal) 
match the last two bytes of the meter’s MAC address (hex).
4
NOMINAL VOLTAGE must be set to your system’s nominal voltage to 
activate the meter’s power quality features.
Step 9: Verify Meter Operation
The LEDs on the back of the meter flash during communications. 
DI
SP
LA
Y
SETUP
UPDATE RATE
Sets when the display updates 
1 to 6 (seconds)
1
CONTRAST
Higher numbers are sharper
0 to 9
7
DELTA VECTORS Specifies how vector diagrams are 
displayed when in Delta mode
System or Instrument
System
LANGUAGE
Specifies the language used on the 
meter’s front panel
English, Spanish, French, 
Russian
English
TIM
E SETUP
TZ OFFSET
Sets the time zone of the meter’s 
location, relative to UTC
- 12:00 to +13:00
+00:00
DST OFFSET
Sets the daylight savings time offset 
of the meter’s location
-3:00 to +3:00
+00:00
SYNC SOURCE
Sets the port to receive time 
synchronization signals
Ethernet, COM1, COM2, 
COM3, COM4
COM1
SYNC TYPE
Specifies whether time sync signals 
are received in local time or UTC
Local Time or UTC
UTC
CLOCK SOURCE Specifies time sync source
Internal, Line Freq or COMM
Line Freq
LOCAL DATE
Sets the local date
Same as Date Format setting
LOCAL TIME
Sets the local time
SEC
U
RITY
SE
TU
P
PASSWORD
Sets the meter password
00000000 to 99999999
00000000
ENABLED
Enables or disables meter security
Yes or No
No
WEB CONFIG
Enables or disables web browser 
configuration of the meter
Enabled or Disabled
Enabled
WEB ACTIVE
Enables or disables internal web 
server on the meter
Yes or No
Yes
Menu
Setting
Description
Range (Values)
Default 
LED
Color
Function
Ethernet 100 (Speed)
Green
Off = link at 10 Mb, On = link at 100 Mb
Ethernet TX
Green
Blinking indicates Ethernet transmission
Ethernet RX/LINK
Green
On = link up, Off = link down
Blinking indicates Ethernet reception
Modem DCD
Green
Indicates a carrier signal is detected (active 
connection to the modem)
Modem RI
Green
Indicates a ring is detected by the modem
COM3 (Modem) TX
Yellow
Indicates serial transmission on COM3
COM3 (Modem) RX
Yellow
Indicates serial reception on COM3
COM2 TX
Yellow
Indicates serial transmission on COM2
COM2 RX
Yellow
Indicates serial reception on COM2
COM1 TX
Yellow
Indicates serial transmission on COM1
COM1 RX
Yellow
Indicates serial reception on COM1