CHAPTER 1  RCI Build Procedure 
1.3.3
When an RCI I/O unit is added later
Figure 1.7  When an RCI I/O unit is added later
1
Connect the I/O unit to be added with an RCI cable by using a daisy-chain 
connection (see 
).
Connect an RCI branching connector to the RCI port, and then connect it with an RCI 
cable by using a daisy-chain connection.
Connect an RCI terminating resistor to the branching connector at either end of the 
2
Turn on the AC input to all the units which are in the RCI connection.
3
Log in to the XSCF Shell.
4
Execute the setrci -c addconfig command to configure the RCI.
5
Execute the setrci -c stat command to display the RCI status.
6
Verify that the added I/O unit is incorporated.
XSCF> setrci -c addconfig
The command completed successfully
XSCF> setrci -c stat
HOST
 address 000101ff
 Active
LIST
 address   pwr  alm   I/F   sys-phase   ctgry  dev-cls sub-cls tm-out
 000101ff OFF   -    ACT    --            host   0001    0a      - 
 003001ff OFF   -    ACT    --            disk   0400    04      -
 003002ff OFF   -    ACT    --            disk   0400    04      -
The command completed successfully
RCI I/O unit
RCI I/O unit
Addition
RCI Host