LST RL58-1 Leaflet

Page of 2
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
RL58_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
Specifi cations
The  fi re  detection  control  panels  Series  BC216  and 
BC016, respectively, provide 16 freely programmable 
open-collector control outputs. Eight of these outputs 
are connected to a fl at cable connector. The Relay Mo-
dules RL58-1 and RL58-2 allow for the easy conversion 
of these control outputs to dry changeover contacts. 
The componentry is connected to the fi re detection con-
trol panel via a fl at cable.
The RL58-1 provides eight relay outputs with a maxi-
mum contact rating of 30W. The current is limited to 1A 
and the voltage is limited to 60VDC. The RL58-2 offers 
four relay outputs with a maximum of 5A/230VAC. The 
terminal of the RL58-2 are designed for mains voltage. 
Two relay modules RL58-2 are each cascadable via pin 
connectors. The relay module is delivered with fl at ca-
ble and mounting accessories for easy installation.
•   8 or 4 relay outputs, respectively, 
with one dry changeover contact 
each
•   Actuation display by LED for each 
output
•  Switch contacts on terminals
•   Easy mounting on componentry 
carrier
•   Connection with control panel via fl at 
cable
Operating voltage 
20 – 31VDC
Current consumption at 24V 
typ. 22mA per activated circuit
Control current 
typ. 1.2mA per input
Ambient temperature 
-5°C to +50°C
RL58-1
Switching power per contact 
1A/60V/30W
Contact life 
 approx. 5 mill. switching cycles (unloaded)
approx. 300,000 switching cycles (at 24VDC/1A)
Dimensions L × W × H 
85 × 65 × 37 (mm)
Weight 
330g
Part No. 
222004
Order name 
Relay Module 8-Fold/60VDC RL58-1