8.4.  Sample UDP/TCP Configurations 
These are actual sample cases.  They are provided as a guideline to aid your configuration 
planning. 
8.4.1. 
Case 1 – Semi-intelligent RTU 
The host device is a Remote Terminal Unit (RTU) designed for industrial control and monitoring 
applications. 
It provides an ASCII user interface, terminating lines with <LF><CR>.  The unit can accept 
single characters as commands; responding to unrecognized characters with a single prompt line 
showing the valid command characters.  The device cannot issue AT commands, and cannot 
process modem result codes.  The messages from the device do not contain the characters “AT” in 
sequence so its messages will not be processed by the modem’s command state processor. 
The device will generate a message whenever an input value changes.  These messages are 
unsolicited status reports.  The device can also issue status reports on request. 
This situation suggests that the device should be configured as a UDP server, without a session 
timeout, and with the Server Receive Lock enabled.  The device will remain in an open session, 
sending unsolicited status to the last calling client.  The Server Receive Lock allows the user to 
change monitoring systems (clients) if needed, or to call the device from multiple systems. 
Other configurations are possible, including closed sessions, since the unsolicited messages from 
the RTU are harmless to the modem’s command processor. 
Cabling 
The RTU is configured as DTE meaning that it is designed to connect directly to a modem.  
However, the unit does not support bi-directional flow control using RTS/CTS.  It uses the 
outmoded application of RTS, only asserting RTS when it wants to transmit.  The DART 300 will 
not send the device any data unless RTS is active; an indication to the DART that the local host is 
ready to receive.  The RTU can operate using only Rx, Tx, and GND. 
To use the RTU with the DART 300, the DART must see asserted RTS and DTR signals.  This 
cable will assert both of these. 
The cable’s DCE end has a male connector and plugs into the modem.  The DTE end has a female 
connector on the cable and plugs into the RTU. 
 
DCE (male)  
DTE 
(female) 
1 DCD 
Not Connected 
1 DCD 
2 RxD 
 
2 RxD 
3 TxD 
 
3 TxD 
4 DTR 
 
4 DTR 
5 GND 
 
5 GND 
6 DSR 
 
6 DSR 
7 RTS 
 
7 RTS 
8 CTS 
Not Connected 
8 CTS 
9 RI 
Not Connected 
9 RI 
Figure 8-1:  Cable Without DTE-DCE Flow Control. 
Rx, Tx, and GND are straight through (DTE to DCE).  The modem’s DSR is tied back to RTS and 