Emerson P/N 400518-02 User Manual

Page of 178
110
Epsilon EP-I Indexing Drive and FM-2 Indexing Module Reference Manual
Fault Codes
A number of diagnostic and fault detection circuits are incorporated to protect the drive. Some faults, like high DC bus and 
amplifier or motor over temperature, can be reset with the Reset button on the front of the drive or the Reset input function. 
Other faults, such as encoder faults, can only be reset by cycling power “Off” (wait until the diagnostics display turns “Off”), 
then power “On”.
The drive accurately tracks motor position during fault conditions. For example, if there is a “Low DC Bus” fault where the 
power stage is disabled, the drive will continue to track the motor’s position provided the logic power is not interrupted.
The +/- Limit faults are automatically cleared when the fault condition is removed. The table below lists all the fault codes 
in priority order from highest to lowest. This means that if two faults are active, only the higher priority fault will be displayed.
Stall Foldback
(EN drive only)
Drive output current is limited to 80 percent of drive stall current.
Ready to Run
Drive enabled, no Stop input.
Display
Fault
Action to Reset
Bridge Disabled
Flash Invalid
Reprogram the Flash
Yes
Drive Overtemp
(Epsilon drive only)
Allow Drive to Cool down,
Cycle Power or Cycle 
Logic Power
Yes
Power Up Test 
Cycle Power or Cycle 
Logic Power
Yes
NVM Invalid
Reset Button or Input Line
Yes
Invalid Configuration
Reset Button or Input Line
Yes
Power Module
Reset Button or Input Line
Cycle Logic Power (MDS)
Yes
High DC Bus 
Reset Button or Input Line
Yes
Low DC Bus 
Reset Button or Input Line
Yes
Encoder State
Cycle Power or Cycle 
Logic Power
Yes
Display Indication
Status
Description