Epsilon EP-I Indexing Drive and FM-2 Indexing Module Reference Manual
Power Dissipation Calculation
Calculating actual dissipation requirements in an application can help minimize enclosure cooling requirements, especially 
in multi-axis systems. To calculate dissipation in a specific application, use the following formula for each axis and then total 
them up. This formula is a generalization and will result in a conservative estimate for power losses.
Where:
TPL = Total power losses (Watts)
TRMS = RMS torque for the application (lb-in)
Vmax = Maximum motor speed in application (RPM)
Pld = Logic Power Losses Drive (Watts)
Psr = Shunt Regulation Losses (Watts)-(RSR-2 losses 
or equivalent)
Note
TRMS * Vmax / 1500 = Power Stage Dissipation = Pp
A more accurate calculation would include even more specifics such as actual torque delivered at each speed plus actual shunt 
regulator usage. For help in calculating these, please contact the Application Department at Control Techniques with your 
system profiles and loads.
Psr
 
 
Pld
 
 
1500
 Vmax
 
TRMS
 
 
TPL
+
+
=