Installation
510977
18
Grounding Information
This dryer must be connected to a grounded 
metal, permanent wiring system; or an 
equipment-grounding conductor must be run 
with the circuit conductors and connected to the 
equipment-grounding terminal or lead on the 
dryer.
The dryer has its own terminal block that must be 
connected to a separate branch, 60 Hertz, single 
phase circuit, AC (alternating current) circuit, 
fused at 30 Amperes (the circuit must be fused 
on both sides of the line). Electrical service for 
the dryer should be of maximum rated voltage 
listed on the nameplate. Do not connect dryer 
to 110, 115, or 120 Volt circuit.
Heating elements are available for field 
installation in dryers which are to be connected to 
electrical service of different voltage than that 
listed on nameplate, such as 208 Volt.
If branch circuit to dryer is 15 feet (4.57 m) or 
less in length, No. 10 AWG wire (copper wire 
only), or as required by local codes. If over 15 
feet (4.57 m), use No. 8 AWG wire (copper wire 
only), or as required by local codes. Allow 
sufficient slack in wiring so dryer can be moved 
from its normal location when necessary. 
The power cord connection between wall 
receptacle and dryer terminal block IS NOT 
supplied with dryer.
 Type of power cord and 
gauge of wire must conform to local codes.