Campbell Hausfeld COM220 User Manual

Page of 36
Appendix A.  Changing COM220 Settings 
 
TABLE A-1.  Selecting ME 
Baud-rates via DIP Switches 3 and 4 
ME Baud-rate 
Switch 3  Switch 4 
9600 Open 
Open 
38400 Open 
Closed 
57600 Closed 
Open 
115200 Closed 
Closed 
 
Please note that older dataloggers (e.g. CR10X, CR23X, CR510) cannot 
support the highest COM220 ME baud-rates.  Table A-2 lists maximum 
datalogger baud-rates. 
TABLE A-2.  Maximum Datalogger ME Baud-rates 
Datalogger Max 
Baud-rate 
CR10X, CR510, CR7, CR21X 
9600 
CR23X 38400 
CR5000 57600 
CR800, CR1000, CR3000  
115200 
 
DIP Switch 5: PakBus Ready 
Switch 5 should be open (default) for PakBus dataloggers (e.g., CR800, 
CR1000, CR3000, CR10XPB, CR23XPB, CR510PB), but must be closed for 
non-Pakbus dataloggers (e.g., CR10X, CR23X, CR510, CR5000).  This switch 
determines if the clock/handshake line is used to detect the ME-PAUSE state.  
DIP Switches 6 and 7: Not used 
DIP Switch 8: Configuration Mode 
Closing DIP switch 8 (and cycling power to the COM220) places the COM220 
in configuration mode.  The COM220 can be configured using an SC532 or an 
SC532A with a 12V AC adapter (part number 15966) and Device 
Configuration utility ver 1.6 or newer and Hayes AT Commands (see below). 
A.2  Hayes AT Commands 
In order to configure the COM220 with Hayes AT commands, you will need 
the Campbell Scientific Device Configuration utility ver 1.6 or newer and a 
SC532 or SC532A device.  An SC12 cable must be connected to the peripheral 
port on the SC532 or SC532A and the CS I/O port on the COM220.  Another 
cable should connect the “RS232” port (if using an SC532 device) or the “PC” 
port (if using an SC532A device) to one of your computer's serial ports.  If 
using an SC532A device, power will be provided to the modem by the SC532A 
with a 12V AC adapter (Figure A-1).  However, if using the older SC532, you 
must apply 12 V to the COM220 via the green connector. 