Apollo 1500 User Manual

Page of 17
11 
635/636 CONTROL BOARD ADJUSTMENTS
 
PROGRAM SWITCHES 
 
  
       Factory    Description 
         Setting 
 
#1 
ON 
TIMER TO CLOSE - Automatically closes gate 
 
 
ON - Close timer enabled    OFF - Close timer disabled 
 
#2 
OFF 
CURRENT SENSITIVITY OPTION - Delays current sensing from start 
 
 
ON - 4 second delay    OFF - 2 second delay 
 
#3 
ON 
TIMER TO CLOSE OPTION  
 
 
ON - timer to close works only when open limit switch is activated 
 
 
OFF - timer to close works from any open gate position 
#4 
OFF 
DUAL CONTROL SLAVE OPTION 
 
 
ON - disables slave side of dual board 
 
 
OFF - enables slave side of dual board 
#5 
OFF 
DUAL CONTROL MASTER OPTION 
 
 
ON - disables master side of dual board 
 
 
OFF - Enables master side of dual board 
#6 
OFF 
MAXIMUM RUN TIMER OPTION 
 
 
ON - stops and reverses gate if run timer times out before closing 
 
 
OFF - stops gate if run timer times out before closing 
#7 
ON 
MAXIMUM RUN TIMER VALUE 
 
 
ON - 40 seconds 
 
 
OFF -20 seconds 
#8 
ON 
TIMER TO CLOSE VALUE 
 
 
ON - 20 to 70 seconds (adjustable) 
 
 
OFF - 10 to 35 seconds (adjustable) 
#9 
OFF 
OPEN, STOP, CLOSE CONTROL ENABLE 
 
 
ON - allows for open, stop, close unit (optional) to operate gate 
 
 
OFF - normal operation 
 
 
(If 9 is on, terminals 4 & 5 must be normally closed for proper operation.)   
 
TIMER TO CLOSE ADJUSTMENT 
 
Rotate clockwise to increase time before gate closes. 
Rotate counter clockwise to decrease time before gate closes. 
If program switch #3 is on, the gate must activate the open limit 
switch in order for the timer to close to operate. 
CURRENT SENSITIVITY 
 
Rotate clockwise to decrease sensitivity (more force). 
Rotate counter clockwise to increase sensitivity (less force). 
WARNING: The CURRENT SENSITIVITY should be adjusted to 
prevent injury in the event of someone being entrapped in the gate. 
This feature should be periodically tested to assure proper operation. 
Refer to SAFETY PRECAUTIONS. 
TIMER 
TO 
CLOSE 
CURRENT 
SENSITIVITY 
Fuses 
 
There are 4 standard automotive type fuses on the 635/636 circuit 
board. The EMERGENCY BY-PASS plug is protected by a 15 Amp 
fuse. The remaining three fuses (one for each of the 12 Volt outputs)  
are 3 amp. 
LED ENABLE 
LED ENABLE 
Enables LEDs for installation and troubleshooting (must be de-
pressed to observe LEDs). 
OFF 
ON