SSC Series Central Chilling Stations 
7-5  Viewing and Operating Chiller Pumps 
If your chiller system was configured to operate the pump(s) of the 
chilled water pump tank the user may view the status of the 
process and recirculation pumps. 
 
Viewing Chiller Pump Status 
To view the status of the pumps, start from the Main Menu, then: 
 
n  Press the 
 or 
 buttons to highlight either “
PROC 
PUMP STATUS”or “RECIRC PUMP STATUS”. 
n  Press 
 
The Pump Status Screen appears 
 
 
Pump Status Screen 
 
Only pumps that are included in the system will be shown on this 
screen.  Pumps will display one of the following states: 
 
1.  OFFLINE – This indicates that the pump has been turned off in 
the pump enable/disable screen.  The pump will not be called 
to operate until it has been re-enabled. 
2.  READY – Indicates that the pump is enabled and ready to run.  
However, the current number of pumps specified to run does 
not require this pump to operate. 
3.  RUNNING – Pump is currently running. 
4.  FAULT – A safety on the pump indicates a fault condition and 
the pump has been deactivated.  Once the problem is remedied, 
the pump will return to a READY state unless it is put in the 
OFFLINE state.