SterlingTek A0551797 User Manual

Page of 86
                      SSC Series Central Chilling Stations  
Page 9 of 86 
 
1-5  Available Options 
SSC Series central chillers are available with options to tailor the 
unit to your requirements. Some are factory installed; some can be 
retro-fitted in the field. Consult Sterling sales for more 
information. Available SSC Series options include: 
 
  Advanced control package including: AB SLC 5/04 PLC with 
PanelView 1000 color touch screen, control of up to nine 
additional chillers, cooling tower system, water treatment 
system, and DH+ communication capabilities 
  General Fault audible/visual alarm with elevated light stack 
  Non-fused rotary thru-the-door disconnect switches 
  Electrical operation available in 208, 460, and 575 volts, 60 
Hz; 200, 380, and 415 volts, 50 Hz 
  UL/
C
UL-listed electrical subpanel 
  Water cooled condenser manifold 
  Onsite startup 
Standard Features on Remote Condensers 
  Direct-drive 3-phase fan motors with ball bearings and internal 
overload protection 
  Electronic variable-speed control of lead fan and fan cycling 
for constant condenser head pressure control 
  Fans are 30” (76 cm) in diameter and have PVC-coated steel 
fan guards; 1½ hp (1.12 kW) variable-speed fans are 26” (66 
cm) in diameter 
  Internal baffles between fan cells 
  UL listed in the United States and Canada 
  Patented floating tube coil to eliminate tube sheet leaks 
  Copper tube condenser coils have corrugated aluminum fins 
  Weather-proof control panel with factory-mounted door 
interrupt switch 
  High-efficiency condenser coil, designed for optimum 
performance 
  Aluminum housing provides corrosion protection for outdoor 
applications