Instructions For Tape Shielded Cable
2.0 Prepare Cable
2.1  Check to be sure cable size fits within kit size range as shown in Table 1.
2.2  Prepare cable using dimensions shown in Figure 1. Refer to Table 2 for semi-con cutback dimension.             
BE SURE TO ALLOW FOR DEPTH OF TERMINAL LUG. If necessary to prevent tape shield from 
unrolling, hold down edge with a single wrap of 3M™ EMI Copper Foil Shielding Tape 1181. 
NOTE: Provide additional exposed conductor distance to account for growth during crimping of ALUMINUM 
lugs or connectors as follows:
Aluminum Connector 
Growth Allowance
2 - 350
1/4” (6 mm)
400 - 650 
1/2" (13 mm)
750–1000 
3/4" (19 mm)
NOTE: It is imperative to remove all remnants of the semi-con layer, even if the semi-con layer comes off as one 
layer. There should not be any remaining black areas, or particles, on the cable insulation layer.
Kit Number
Insulation 0.D.
15 kV 
AWG / kcmil
25/28 kV 
AWG / kcmil
35 kV 
AWG / kcmil
Semi-con  
Cutback
7685-S-8
1.05" -1.46"
(26,7 - 37,1 mm)
500-700 
(240 - 400 mm
2
)
250-500 
(125 - 250 mm
2
)
3/0-350 
(95 - 150 mm
2
)
13.5" 
(342,9 mm)
1.24" - 1.80"
(31,5 - 45,7 mm)
750-1000 
(400 - 500 mm
2
)
600-800 
(300 - 400 mm
2
)
500-600 
(185 - 325 mm
2
)
 13.0" 
(330,2 mm)
Table 2
1 1/ 2”
(38 mm)
Jacket Removal Length
3” (76 mm)
Semi-Con
Tape Shield
Depth Of Terminal Lug + Growth Allowance
Cable Jacket
Semi-Con Cutback
Figure 1