Honeywell MS4103 User Manual

Page of 268
120
M6435; M7435
Cartridge Globe Valve Spring 
Return Actuators are small electric 
actuators for individual room 
control that provide floating or 
modulating control of 1/2 and 3/4 
in. V5852, V5862 two-way or 
V5853, V5863 three-way valves.
SPECIFICATIONS
Actuator Type ....................................... Valve
Control Signal ....................................... Floating; 0-10 Vdc or 
2-10 Vdc modulating
Fail Safe Mode  ..................................... Spring Return, operator 
retracts up (Normally open for 
1/2 in. and 3/4 in. V5852 and 
V5862. Normally closed for all 
other V58XX valves.)
Cable Entry  .......................................... Threaded conduit connector
Electrical Protection  ............................. Class I Insulation (24 Vac)
Ingress Protection Rating ..................... IP54
Electrical Connections  ......................... Screw terminals
Feedback  ............................................. No
Frequency  ............................................ 50 Hz, 60 Hz
Manual operation  ................................. Use valve dust cap
Mounting  .............................................. Threads onto V58XX valve 
bonnet
Stroke  ................................................... 1/4 in. (6 mm) 
Supply Voltage  ..................................... 24 Vac +20%, -15%
Number of Internal Auxiliary Switch ..... 0
Materials ............................................... Low Maintenance Plastic 
Housing
Operating Humidity Range (% RH) ...... 5 to 95% RH
Medium Temperature  ........................... 266 F Maximum (130 C 
Maximum) 
Ambient Temperature Range  ............... 32 F to 122 F (0 C to 50 C) 
Storage Temperature Range ................ -40 F to 158 F (-40 C to 70 C) 
Weight  .................................................. 1.1 lb (0.5 kg) 
Includes  ............................................... 1/2 in. conduit hub
APPROVALS
Underwriters Laboratories, Inc.  ........... UL94-5V
FEATURES
• Stem actuator retracts up on power failure. Fail safe mode 
depends on valve seat rest position. 
• Suitable for Excel/IRC system or other controllers providing 
specified signals. 
• Magnetic coupling for torque limitation independent of 
voltage supply and self-adjustment of the close-off port. 
• No mounting tools required. 
• Compact size allows installation in limited space of fan coil 
units, induction units, and small reheaters or recoolers. 
• Visual position indication (red disk).
DIMENSIONS DIAGRAM
5
(126)
1-5/16
(33)
3-3/16 (81)
M19615
4-1/4 (108)
Unitary Valve Actuator
m6435; m7435