Honeywell MS4103 User Manual
60
Flanged Globe Valves 2½- 3"
With Pneumatic Actuators
Common Features
• Rolling diaphragm for long life and low hysteresis
• Easily installation and attachment to the valve
• Direct or reverse acting
• No positive positioner
• Easily installation and attachment to the valve
• Direct or reverse acting
• No positive positioner
Actuator Features
Without Positive Positioner
Actuator O.S. Number
MP953C1067
MP953C1075
MP953C1083
MP953C1554
MP953C1562
MP953D1107
MP953D1131
MP953D1172
Direct / Reverse Acting DA / RA
DA
DA
DA
DA
DA
RA
RA
RA
Diaphragm Size
8"
8"
8"
13"
13"
7-1/8" 7-1/8" 7-1/8"
Fail Safe Action
Stem Up Stem Up Stem Up Stem Up Stem Up Stem
Down
Stem
Down
Stem
Down
Positioner
10psi span
5psi span
3psi span
3psi span
Valve Size
(inches)
Cv
Valve
Type
Max Static
Water Pressure
ANSI
Class
Max Steam
Pressure
Flow
Characteristic
Valve
Action
Valve OS
Number
Close-off Pressure - See Charts On Page 55
2-W
ay W
ater & Steam Valves
2-1/2"
63
Standard
250 psi
125
15 psi (2-position)
Equal %
Stem down to close
V5011A1734 M*-NO M*-NO M*-NO P*-NO P*-NO N*-NC N*-NC N*-NC
70 Pressure Balanced
175 psi
125 psig / 353 F
Equal %
VGF21EP25 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
70
Standard
Equal %
VGF21ES25 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
72 Pressure Balanced
Linear
VGF21LP25 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
70
Standard
Linear
VGF21LS25 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
70
Standard
400 psi
250
Equal %
VGF22ES25 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
3"
100
Standard
250 psi
125
15 psi (2-position)
Equal %
V5011A1767 M*-NO M*-NO M*-NO P*-NO P*-NO N*-NC N*-NC N*-NC
115 Pressure Balanced
175 psi
125 psig / 353 F
Equal %
VGF21EP30 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
115
Standard
Equal %
VGF21ES30 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
120 Pressure Balanced
Linear
VGF21LP30 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
125
Standard
Linear
VGF21LS30 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
120
Standard
400 psi
250
Equal %
VGF22ES30 L*-NO
L*-NO
L*-NO
O*-NO O*-NO R*-NC
R*-NC
R*-NC
3-W
ay W
ater
Valves
2-1/2"
63
Mixing
250 psi
125
N/A
Constant Total
Stem up closes A-AB
V5013B1003 S-NC
S-NC
S-NC
T-NC
T-NC
U-NO
U-NO
U-NO
63
Diverting
250 psi
Constant Total
Stem up closes B-AB
V5013C1001 S-NC
S-NC
S-NC
T-NC
T-NC
U-NO
U-NO
U-NO
70
Mixing
175 psi
Equal % A-AB
Stem up closes A-AB
VGF31EM25
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
70
Diverting
175 psi
Linear, Constant Total Stem up closes B-AB
VGF31LD25
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
70
Mixing
400 psi
250
Equal % A-AB
Stem up closes A-AB
VGF32EM25
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
70
Diverting
400 psi
250
Linear, Constant Total Stem up closes B-AB
VGF32LD25
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
3"
100
Mixing
250 psi
125
Constant Total
Stem up closes A-AB
V5013B1011 S-NC
S-NC
S-NC
T-NC
T-NC
U-NO
U-NO
U-NO
100
Diverting
250 psi
Constant Total
Stem up closes B-AB
V5013C1019 S-NC
S-NC
S-NC
T-NC
T-NC
U-NO
U-NO
U-NO
120
Mixing
175 psi
Equal % A-AB
Stem up closes A-AB
VGF31EM30
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
120
Diverting
175 psi
Linear, Constant Total Stem up closes B-AB
VGF31LD30
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
115
Mixing
400 psi
250
Equal % A-AB
Stem up closes A-AB
VGF32EM30
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
120
Diverting
400 psi
250
Linear, Constant Total Stem up closes B-AB
VGF32LD30
L-NC
L-NC
L-NC
O-NC
O-NC
R-NO
R-NO
R-NO
*The close-off pressure not to exceed rated pressure of steam valve
NC = Normally Closed
NO = Normally Open