EXCEL 50/100/500/600/800 
EN2B-0092GE51 R1111 
 
DATAPOINTS 
An Excel 50/100/500/600/800 system can have the following number of datapoints: 
 
•  Excel 50: 
22 physical (onboard I/Os) plus up to 46 physical LON I/Os 
•  Excel 100: 
36 physical (onboard I/Os) 
•  Excel 500: 
128 physical I/Os, extendable via L
ON
W
ORKS
 I/Os 
•  Excel 600: 
128 physical I/Os 
 
Furthermore, Excel 50/100/500/600 support an additional 256 pseudo datapoints. 
 
Excel 800: 
381 datapoints (random mix of physical and pseudo datapoints) 
 
A datapoint has different attributes according to its type. Attributes are displayed 
and modified on the XI581 (not with XCL5010, Excel 100C), XI582, and the PC-
based XL-Online operator interfaces or on the Excel 50 MMI. Attributes contain 
information about the given datapoint. This information could be: 
 
•  Input limits values 
•  Operating status 
•  Current temperature 
•  Elapsed run time 
 
The following sections provide more-detailed information about the different kinds of 
datapoints and datapoint attributes and explain which attributes are assigned to 
which datapoints. 
 
 
Physical Datapoints 
Physical datapoints are inputs and outputs attached to hardware devices like 
sensors and actuators. 
 
 
Fig. 2. Physical datapoint symbols 
The following are examples of physical datapoints 
 
 
Analog inputs 
NTC, PT 1000, PT 3000, BALCO Sensors (PT 3000/BALCO not with Excel 100C), 
standard 0 (2)...10 V and 0 (4)...20 mA input, to connect e.g. outside air 
temperature sensors. 
 
 
Analog outputs 
Outputs with a continuous 0...10 V output signal for controlling continuous actuators 
(Excel 100C supplies up to 20 mA on the analog outputs). 
 
 
Digital inputs 
Inputs for processing voltage-free signals (switches, contacts). 
 
 
Digital outputs (not Excel 100C) 
Outputs for driving three-position actuators, for example, a damper motor; two 
position devices, for example, a circulation pump; 0...10 V and pulsed outputs 
 
 
Totalizer inputs 
Digital inputs for processing pulsed signals up to 20 Hz (depending on Distributed 
I/O module specifications), for example, metered energy consumption.