Honeywell R0512 User Manual

Page of 86
EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
15 
 
digital input 
CARE interpretation  
(control table) 
 
 
 
 
display at operator interface 
(status text) 
OFF/ 
trouble: 
alarm 
 
OFF/ 
trouble: 
alarm 
 
ON/ 
operating 
RTN* 
 
ON/ 
operating 
RTN* 
 
* RTN = Return To Normal 
 
 
Alarm Delay 
 
Delaying alarm outputs 
The alarm delay time (in seconds) is entered in the attribute "Alarm Delay". The 
alarm delay time determines how long an alarm condition must exist before an 
alarm is generated. Entering an alarm delay time of 10 seconds means that the limit 
value must be exceeded for at least 10 seconds before this datapoint generates an 
alarm. If the limit value lasts for only 7 second, then no alarm occurs. 
 
 
Alarm Suppression 
The attribute “Suppress Alarm” establishes whether or not alarm messages from 
the following alarm attributes should be suppressed: 
•  Operational status 
•  Min/Max. limit 
•  Maintenance alarm 
•  Interval counter 
•  Alarm Status 
 
The following entries are possible: 
 
•  Off 
Alarms not suppressed 
•  On 
Alarms suppressed 
 
 
Digital input example 
In addition to a variety of other attributes, a digital input also has the "Operating 
Mode", "Alarm Status", and "Maintenance Alarm" attributes. If alarm suppression is 
activated for this datapoint, then no message is displayed during an operating mode 
change-over, or when changing into the alarm condition, or when reaching the 
maintenance alarm. 
 
 
Suppression of system 
The controller will not issue a system alarm when the alarm’s system alarm text 
 
alarms (V2.04.xx or higher) 
starts with an @ character. 
 
 
Alarm Status (prior to V2.04.x) 
 
Alarm monitoring 
In the case of a digital input or a pseudo digital point, the attribute "Alarm Status" 
specifies whether or not alarm monitoring is required. 
The following entries are possible: 
 
•  Yes:  Alarm monitoring is required 
•  No: 
Alarm monitoring is not required 
 
When alarm monitoring is required, the alarm message occurs when the digital 
point changes from the active state to the passive state (alarm reached). An 
additional message is generated (alarm going) when the digital point returns to the 
active state  
(see Fig. 6. Alarm status messaging) 
 
 
 
 
 
Alarm 
reached 
Alarm 
ending