ALARM HANDLING 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
48 
 
Alarm 
no. 
alarm text 
English) 
cond. 
code # 
cause/reason 
                                                                                                                               
48 
Part applic. miss 
46 
47 
48 
49 
52 
1) No RACL program. 
2) No parameter file. 
3) No Z register file. 
4) No T register file. 
5) No datapoint description. 
49 
RACL environ fault 
26 
1) Submodule does not exist. 
27 
2) Parameter file missing. 
28 
3) No M0 module. 
31 
4) Invalid SKIP destination. 
34 
5) Info points STARTUP, SHUTDOWN, or EXECUTING_STOPPED are missing or 
 
6) During RACL start datapoint contains errors. 
7) freely programmable application loaded into Excel 50 controller (system alarm 
parameters set to 0,0,0). 
50 
INIT div. by zero 
14 
Reason of new start: Division by zero. 
51 
INIT under OpCode  15 
Reason of new start: the system software contains an undefined Operation Code. 
52 
Power failure 
16 
Reason of new start: power failure, data in RAM ok. 
53 
Link Config Bad 
Xlink alarm. 
54 
I/O board missing 
19 
The required configuration contains at least one module which is not included in the 
hardware configuration. 
55 
Unused I/O board 
18 
The hardware configuration contains at least one module that is not needed (can be taken 
out). 
56 
HW Config. failure 
20 
1) Hardware Configuration file (.kfx file) not complete loaded. 
2) Different modules are plugged under the same address (set using the rotary HEX 
switch) in the required configuration and in the hardware configuration. 
3) An application containing NV-mapping is rejected by the target controller because the 
hardware does not have the 3120E5 Neuron® chip. 
57 
Wrong version no. 
21 
The version number of the application files and the configuration file are not the same. 
58 
Totalizer overflow 
Overflow operation hours counter, point value of counters and interval impulse counter. 
59 
Maintenance alarm  7 
Course of a service interval for digital points or course or the message/calling interval for 
counters. Call intervals for counters. 
60 
Undef. RACL input  62 
Undefined RACL errors. 
61 
Too many Globals 
63 
The loaded application contains too many remote points. An application with more than 46 
NVs has been rejected for download into an Excel 50 freely programmable controller 
located on a L
ON
W
ORKS 
network. 
62 
C-Bus error 
64 
Communication defect/disturbance between Excel 500 and C-Bus submodule. Logical 
modem device in controller has gotten a C-Bus # already in use for a C-Bus controller. 
63 
No Globals 
memory 
No remote storage; the remote controller has no storage left for requested remote points. 
64 
Global pnt missing  10 
The user address of the remote point was not found in the remote controller. 
65 
Glob Pnt Occupied  11 
A remote output to a remote controller is already assigned to another controller. 
66 
CPU stopped 
12 
The remote controller is in stopped condition. 
67 
CPU not available 
13 
The remote controller is switched off or does not respond to C-Bus communication. 
68 
Init. actuators 
65 
Floating outputs (3-position outputs) are synchronized. 
69 
WARM START 
66 
Reason of new start: watchdog. 
70 
COLD START 
67 
Reason of new start: power failure, data in RAM destroyed. 
71 
Point in manual 
68 
When falling back to password level 3 there are still points in manual override. 
72 
Report too large 
69 
Not enough space in the report file for initialization. 
73 
XI 581 required 
70 
After a download, an entry is demanded in the initializing phase of the ASPECD 
application. This can happen only with XI581 emulation. 
74 
New appli. loaded 
74 
Download of a new application part or entire application.