D9412GV2/D7412GV2 | Operation and Installation Guide | 4.0  Installation 
 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
17 
 
4.5.3 
Enabling Ground Fault Detection 
To configure the D9412GV2 and D7412GV2 Control 
Panels to enable ground fault detection: 
1. 
Set the silent relay in Area 5 to any value from 1 
to 128. 
Do not use a zero (0) value. 
 
 
The default value for the Area 5 silent relay 
is 0 (zero). The 0 value disables the ground 
fault detection function. 
2. 
Close Switch S4 (Figure 3 on page 16). Refer to 
Table 5 for information about the conditions for 
enabling and disabling the Ground Fault 
Detection Circuit. 
Table 5: 
Ground Fault Detection Status 
 
Ground Fault 
Detection Circuit 
Switch S4 
Value of Area 5 
Silent Relay Alarm 
Enabled 
Closed 
1 to 128 
Closed 0 
Disabled 
Open 
0 to 128 
4.5.4 
D9412GV2 and D7412GV2 Ground Fault 
Specifications 
Table 6 provides the impedance specifications for 
detecting ground faults when any terminal or field 
wiring is shorted to ground. 
Table 6: 
Ground Fault Impedance 
Specifications 
 
Impedance 
Control Panel Detects Ground Fault 
≤ 
300 
Ω
 
Yes 
300 
Ω
 to 
200
 
k
Ω
 
No 
 200 k
Ω
 
Detection depends upon the terminal 
4.5.5 
Locking the Reset Pin 
Locking the reset pin disables the control panel  
(Figure 4). When the control panel is disabled, the 
system ignores the keypads and points. 
CALL FOR 
SERVICE
 appears in keypad displays when the pin is 
locked down. 
On-board relays (Terminals 6 and 7) and off-board 
relays deactivate when the control panel is reset. 
Terminal 8 has power when the relay is deactivated. 
Activation interrupts power at that terminal. The on-
board relay (Terminal 8) remains deactivated when the 
reset pin is locked in the disable position. 
Releasing the reset pin from the closed position resets 
the control panel. The control panel resets all its timers, 
counters, indexes, and buffers. Any points that restore 
after a reset do not generate Restoral Reports. 
If the reset pin is placed in the disable position when 
all areas are armed, there must be an entry in the 
Answer Armed program item. Refer to RPS Parameters 
in the D9412GV2/D7412GV2 Program Entry Guide  
(P/N: F01U003636). 
Locking the pin in the disable position applies power to 
the control panel and charges the battery while the 
detection devices and keypads are installed. 
 
Figure 4: 
Reset Pin 
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED
POWER +
YELLOW
DATA BUS A
GREEN
DATA BUS B
BLACK
COMMON
32
31
30
29
1
2
 
1 -  Reset pin locked (closed). 
2 -  Reset pin normal (open).