A D8128D OctoPOPIT can be installed up 
to 61 m (200 ft.) from the control panel. 
2.
 
Connect the D8128D to the control panel: 
 
Wire the D8128D to the terminal strip on the 
side of the POPEX Module (), 
or  
 
Connect the D8128D using the Molex
®
 
connectors (P1 and P2). Refer to Using Molex® 
Connectors
 on page 46. 
 
Caution - AC induction: Avoid installing 
Zonex data wires and Zonex input (sensor 
loop) wires around any AC conduit, wiring, 
or electrical devices that emit fields of 
electromagnetic interference (EMI). 
Using the Terminal Strip 
Refer to Table 17Figure 16 on page 44, and Figure 17 
on page 45 when using the terminal strip to connect the 
D8128D OctoPOPIT to the control panel. 
Table 17: 
Terminal Strip Connections 
D8128D 
D9412GV2 
D7412GV2 
Common 
Terminal 23 
Terminal 23 
Out 
Zonex 1 = Terminal 27 
Zonex 2 = Terminal 25 
Terminal 27 
In 
Zonex 1 = Terminal 28 
Zonex 2 = Terminal 26 
Terminal 28 
+12 V 
Terminal 24 
Terminal 24