Network Safe—This parameter saves or loads network settings for the display that have been 
modified from the factory defaults to an internal file that can be downloaded / uploaded using the 
Liebert iCOM
®
 Service Tool. Selecting “Save” will write the settings to the internal storage file and 
selecting “Load” will write the settings from the internal storage file to the application software.
SW Version—This parameter contains the application software version loaded into the Liebert 
iCOM display.
Figure 82 System / network setup parameters—large display only System - Page 2
IP Address—This parameter contains the network address of the display. This address must be 
unique to every other device on the network.
Netmask—Not currently used.
Gateway—Not currently used.
MAC—The MAC address is a unique hardware identifier of the Ethernet device.
U2U Protocol—This parameter is always set to GBP.
U2U Address—This parameter is a unique identifier for each unit on the network. Display addresses 
range from 33 to 64. Each display on the U2U network must have a different U2U address.
U2U Group—This parameter is used to create zones or groups within a U2U network. Once a group 
number is selected the display will only see other devices with the same group number. The group 
number can be changed to view other devices in different groups.
Bootloader Variables—This parameter indicates if there has been a change to the bootloader since 
it was last loaded. This parameter should only be activated by an authorized service person.
S812
S813
S814
S815
S816
S817
S818
S819
S820
S821
S822
PASSWORD
(Actual Level 0)
????
IP Address
10.203.062.150
Netmask
255.255.255.192
Gateway
10.203.062.129
MAC
00:00:68:19:0B:58
U2U Protocol
GBP
U2U Address
33
U2U Group
13
Bootloader Variables
Changed
No
SYSTEM / NETWORK SETUP (page 2 of 2)
SYSTEM
to change parameter
for next/previous unit
to select parameter
to confirm
then