Emerson BW2 User Manual

Page of 16
IntelliGear Plus Variable Speed MD Gearmotors
10
3.4 Terminal block assignments and MD functionality
Controller 
Terminal 
Number
Designation
Function
Characteristics
1
10V
+10V analog internal source
Accuracy
 ± 2%
Maximum output current
30 mA
Voltage input
2
ADI1
Hand Mode Speed Reference
Full scale voltage
10 V ± 2%
**
Input Impedance
95 kΩ
3
0V
Logic circuit common 0V
Current input
Current range
0 to 20 mA ± 5%
4
ADI2
Auto Mode Speed Reference
Input impedance
500 Ω
Resolution
10 bits
Sampling
6 ms
 
Logic input (if connected to the +24 V
6
ADIO3
Fault Signal Input
Threshholds
“0”:<5V-”1”; >10V
From Pump Operation
Voltage range
0 to +24V
Run Dry and/or High Pressure Load
95 kΩ
Input threshold
7.5V
Characteristics
Digital output 1
7
DIO1
Alarm LED
Threshholds
“0”:<5V-”1”; >10V
Voltage range
0 to +24V
Sampling/refreshment
2 ms
5
Output current
10 mA in total
Overload current
33 = 150mA, 31/32 = 50mA
24V
 +24V internal source
Accuracy
 ±  5%
11
Protection
Current limiting and overload
fault trip
Logic input 2
Characteristics
Logic input (positive logic)
8
DI2
Run/Stop  
Threshold
“0”:<5V-”1”; >10V
 
Voltage range
0 to +24V
Logic input 3
Motor Thermal Input
Sampling/refreshment
2 ms
9
DI3
Absolute maximum voltage 0 to +35V
range
Logic input 4
Hand Mode Selectior
Load
15 kΩ
10
DI4 
Input threshold
7.5V
Voltage range
9 to + 35V
12
ENA
Enable
Impedance
820 Ω
13
RL1
Drive Healthy Contact
N/C after start-up if OK
 
Characteristics
250VAC maximum contact
current
NO single pole contact
14
RL2
4 A, resistive load
2 A inductive load
** Performs scaling function when drive is programmed for full PI mode of operation
4. Commissioning
WARNING!
 Before switching on the IntelliGear Plus unit, check that the electrical 
connections are correct, and that any moving parts are mechanically guarded.
WARNING!
 For the safety of personnel, the IntelliGear Plus must not be switched on 
with any protective covering removed.