Toro SA41 User Manual

Page of 30
18
SA41 ELECTRICAL SPECIFICATIONS
INVERTER TYPE  PWM Full bridge power stage, with true sine wave AC output.
DEMAND START SECTION
Type:
Pulsing AC
Minimum Load Power to start (User adjustable):
3W to 20W
Maximum response time:
1 sec
Standby current from battery (Average): 
60mA
BATTERY VOLTAGE RANGE
Low DC Volts Disconnect (Instantaneous):
34V
Low DC Volts Cutout (Delayed, User Adjustable):
38-44V
Low DC Volts Cut-in (Delayed, User Adjustable):
44.4-52V
High DC Volts Cutout (Instantaneous, User Adjustable):
60-68V
High DC Volts Disconnect (Instantaneous):
70V
TOTAL APPLIANCE RATING AT
25°C
40°C 
Continuous:
3000W
2800W
30 Minute rating:
4700W
4400W
5 Minute rating:
5300W
1 Minute rating:
6500W
Surge rating:
8500W
INVERTER EFFICIENCY
Peak (at 500W):
91%
No load power consumption (C0NT mode):
0.66 A
MISCELLANEOUS SPECIFICATIONS
Output Frequency Accuracy:
50Hz ± 0.001 %
Output Voltage Accuracy (0 - 2200W)
240V ± 4 %
Total Harmonic Distortion (THD) 
< 4 %
Control Outputs 1 & 2, max DC sinking current:
50 mA
Alarm Inputs 1 & 2, input switching level:
HI  > 3 V
LO < 1 V
Operating temperature range:
-10°C to 50°C
Weight:
32 kg
DC Input is Electrically Isolated from AC Output
Note:  Through a policy of continued development, specifications are subject to change without
notice.
The above specifications are based on unity power factor.