FIELD CONTROLS FDVS User Manual

Page of 4
 
Page 3
I
NSTALLATION 
O
T
HE 
V
ENT 
T
ERMINATION 
C
OMBUSTION 
A
IR 
T
EE
 
1.  Assemble the combustion air tee assembly body to the vent 
termination outer pipe, and rotate to the desired position. Attach the 
tee assembly body to the vent termination outer pipe with at least 3 
sheet metal screws evenly spaced apart (not included). 
2.  After completing assembly of the vent pipe to the termination inner 
pipe (Fig. 4), apply the supplied high temperature sealant to the 
cover pan around the inner pipe, around the joint between the collar 
and the Tee assembly, and seal or tape the joint from the FDVS 
Termination to the Tee assembly. 
NOTE: The tee may be rotated into any position so that the collar is in a 
convenient orientation. 
CLEARANCE TO COMBUSTIBLES:  FDVS Termination: 0", FOVP 
Flexible Oil Vent Pipe: 1".  These clearances are to maintained unless 
superceded by the appliance manufacturer's installation instructions or by 
National and/or local codes (see Step 3).
 
C
ONNECTING THE 
V
ENT 
P
IPE FROM THE 
FDVS 
TO THE 
A
PPLIANCE
 
1.  The venting system should be installed and supported in accordance with the latest version in the USA of the National Fuel Gas 
Code ANSI Z223.1, UL-726, National Fire Protection Association NFPA31, and in Canada CSA B140, CSA B139 Installation Code 
or in accordance with any other local codes or the authority having jurisdiction. Where requirements for venting differ the most 
stringent standard requirements shall apply. A vent pipe connector, designed for positive pressure venting, shall be supported for 
the design and weight of the material employed, to maintain clearances, prevent physical damage and separation of joints. All joints 
MUST be sealed, for positive vent pressure, to prevent flue gas leakage into the structure. 
2.  Route the vent pipe from the appliance to the vent termination using the minimum number of bends as possible. The last horizontal 
section of the vent pipe should have a slight downward slope from the appliance to the vent termination. For clearances to 
combustible materials and other installation requirements, refer to the National Fuel Gas Code ANSI Z223.1, UL-726, NFPA31, 
CSA B140, CSA B139 and/or any applicable local codes or appliance manufacturer's installation instructions. 
3.  Refer to the appliance manufacturer’s specifications for maximum length of vent pipe run. Unless otherwise specified by the 
appliance manufacturer, use the same size diameter pipe as the exhaust outlet on the appliance to connect to the vent termination 
inlet. Use a reducer or increaser, if necessary, at the vent termination to connect the vent pipe. 
4.  Support the Flexible Oil Vent Pipe (FOVP) at regular intervals of maximum 36" spacing with appropriate strapping or hangers, per 
National and local code requirements.  Do not install screws into or otherwise penetrate any part of the vent pipe under any 
circumstances. 
C
ONNECTING THE 
C
OMBUSTION 
A
IR 
I
NTAKE 
P
IPE FROM THE 
FDVS 
TO THE 
A
PPLIANCE
 
1.  Refer to the appliance manufacturer’s specifications for maximum run length of combustion air intake pipe. Unless otherwise 
specified by the appliance manufacturer, use the same size diameter pipe from the FDVS terminal combustion air tee collar to the 
appliance oil burner combustion air inlet (or Air boot, if applicable.) Use a reducer or increaser, if necessary at the burner 
combustion air inlet to connect the combustion air intake pipe. 
2.  The VRV should be installed close to the air inlet of the burner. To install the VRV, refer to the Installation Instructions included with 
the VRV. 
GENERAL INSTALLATION INSPECTION 
Recommended procedures for safety inspection of an appliance should be in accordance with the latest version of the National Fuel 
Gas Code ANSI Z 223.1, UL 726, and the National Fire Protection Association NFPA 31 in the USA, CSA B140 and CSA B139 
Installation Code in Canada. The following procedure will help evaluate the venting system. It is intended as a guide to aid in 
determining that the venting system is properly installed and is in a safe condition for continuous use. This procedure should be 
recognized as a generalized procedure which cannot anticipate all situations. Accordingly, in some cases, deviation from this procedure 
may be necessary to determine safe operation of the equipment. If it is determined that a condition exists which could result in unsafe 
operation, the appliance should be shut off and the owner advised of the unsafe condition. Corrections must be made before the 
appliance is put into continuous operation. The following steps should be followed in making a safety inspection. 
1.  Visually inspect the venting system for proper size and determine that there is no flue gas spillage, blockage, restriction, leakage, 
corrosion, or other deficiency which could cause an unsafe operation. 
2.  Place in operation the appliance being inspected. Follow the lighting instructions and adjust thermostat so appliance will operate 
continuously. 
3.  Determine that the burner is operating properly and that the burner ignition operates satisfactorily by interrupting and re-
establishing the electrical power of the appliance in any convenient manner. Test the burner safety device to determine if it is 
operating properly by disconnecting the flame safety circuit. 
4.  Test for spillage at the burner inlet air location around the VRV after 5 minutes of operation. Use a draft gauge, flame of a match or 
candle, or smoke from a cigarette, cigar or pipe. Shut off appliance thermostat and check for spillage around the VRV. If a flow 
reversal is noticed, house depressurization is occurring and make up air is required. 
MAINTENANCE 
Inspect all  vent connections annually for looseness, evidence of corrosion, or flue gas leakage. Replace, seal, or tighten pipe 
connections if necessary. 
As part of the yearly maintenance schedule, remove the Intake Access Panel on the exterior of the FDVS vent termination (See Figure 
2) and remove any debris or foreign material.  Be sure to properly replace the panel. 
Figure 3 – Top View