2-40 HP Portable Chillers 
Chapter 3: Installation 
18 of 70 
3-3  Process Water Connections 
All of our portable chillers have two chilled water connections. The chilled water supply, 
labeled “To Process” is the outlet for the chilled water leading to the process being cooled. 
The chilled water return, labeled “From Process” is the inlet leading from the process back 
into the chiller to be cooled and re-circulated. 
All external chilled water connections should be run full size to the process. Flow and 
pressure information is available on pages 58-61 in the Appendix.  The largest possible 
openings and passages should be provided for the flow of chilled water through platens, dies, 
molds, or other pieces of equipment. 
Note: 
Be sure to reduce external pressure drop as much as possible by generously 
sizing piping and tooling water passageways. 
3-4 Bypass 
Valve 
Considerations 
Our portable chillers have a spring-loaded bypass valve. If the chilled water shut-off valves 
are inadvertently closed while the chiller is running, the factory-set bypass valve opens and 
allows a small amount of water to flow through the chiller. This action protects the chiller 
from freeze-up and allows the other cutout devices to shut down the chiller. The bypass valve 
is not intended to provide continuous full bypass flow. 
Caution!  Do not attempt to adjust or otherwise tamper with the bypass valve. Your 
warranty will be voided. 
3-5  Galvanic Corrosion Considerations 
The materials used in the water circuit piping of these chillers are non-ferrous and react 
electro-chemically with ferrous metallic materials. Some water has dissolved minerals that 
greatly accelerate the reaction between dissimilar metals. 
PVC or non-ferrous piping is recommended to reduce galvanic action. If iron piping must be 
used, use dielectric unions at the chiller. 
3-6 Water 
Treatment 
Considerations 
Water treatment is an integral part of the system. In some locations, water may cause large 
deposits of scale, erosion, algae, and/or corrosion. 
Note: 
The use of poor quality water may result in inefficient operation, heat 
exchanger damage, and pump seal damage. Consult a qualified water 
treatment specialist to determine whether treatment is needed. 
We offer a complete line of water treatment equipment. Contact your sales representative for 
water testing and treatment options.