3-10  Automatic Water Make-Up Option 
The chiller may be connected to an automatic make-up system if the optional package (float 
switch, pressure regulating, pipe fittings, solenoid valve and 1/2” NPT city water make-up 
connection) is factory installed. 
Refer to the typical piping schematics on pages 64-69 in the Appendix for additional 
components necessary for this installation.  
Note: 
Prevent reservoir over-pressurization by setting the required pressure-
regulating valve to limit make-up water pressure to less than 5 psi. The 
reservoir must remain vented to the atmosphere.
 
If the automatic make-up system is connected to a city water system, make provisions to 
prevent backflow contamination. Install an approved backflow preventer in accordance with 
local codes. 
Caution!  Adding straight city water into a glycol/water mixture dilutes the solution and 
eventually leads to system freeze-up. Damage from freeze-up is not covered by 
the warranty. 
To prevent system freeze-up in automatic make-up applications, we recommend using either 
a chemical feeder or make-up reservoir to replenish glycol. Contact the sales department for 
more information about these configurations.