Sterling A0554831 User Manual

Page of 70
2-40 HP Portable Chillers 
Chapter 7: Appendix 
49 of 70 
2 hp and 3.5 hp Water-Cooled Portable Chillers 
Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton 
(9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water. For 50 Hz applications, multiply capacity by 0.83. Nominal 60 
Hz capacity flow rate must be maintained.
 
 
  
Nominal
 
 
Condenser 
water  
 
Nominal cooling  
water 
Com-  Nominal
Water 
flow in gpm 
Amp draws 
g 
HP capacity 
c in tons 
flow 
pressor
pump 
conn. 
Tower 
City 
460/3/60 
h 
 
no pump 
1 pump 
gpm 
d hp  hp  in. 
NPT 
water 
water f rated running
2 2.1 1.9 5.1 
2.0 
1.0 
1.0” 6.2 4.2 12.2  8.3 
3.5 3.6  3.4 8.6 
3.5 1.0  1.0” 10.5 7.2 
16.4 
11.8 
c  Based on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. Optional additional process 
pump hp (kW) reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power). 
d  Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump. 
e  Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum. 
f  Based on availability of 70ºF (21ºC) city water at 25 psi (172.4 kPa/1.7 bars) minimum. 
g  An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total 
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 
on page 16), and add it to the chiller rated or running amperage. 
h  Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages. 
 
 
2 hp and 3.5 hp water-cooled portable chillers come standard with 2” (63 mm) swivel casters. 
 
  
Process 
 
Weights 
HP 
Compressor connections 
Dimensions in inches 
c  
Dry 
d Shipping 
d Operating 
d e
 hp 
in. 
NPT 
height 
width 
depth 
lbs. 
lbs.  lbs. 
2 2.0  1.0” 
28.3” 
22.0” 41.7”  333 
363 
383 
3.5 3.5  1.0” 28.3” 
22.0” 41.7”  362 
392 
412 
c  To convert to cm, multiply by 2.54. Add to height dimension based on mounting options. 
d  Weight is for standard chiller. Some optional features will increase weight. Multiply by 0.454 to calculate Kg
e  Operating weight is with a full 6-gallon (22.7 liter) reservoir tank of water.