20 hp, 25 hp, and 30 hp Water-Cooled Portable Chillers 
Nominal operating parameters for water-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton 
(9.1 lpm per 3.517 kW) with 85ºF (29ºC) tower water. For 50 Hz applications, multiply capacity by 0.83Nominal 60 
Hz capacity flow rate must be maintained. 
 
 
Nominal cooling  
Nominal  Com- 
 
Condenser water 
Power in amps 
g 
 capacity 
c tons 
water 
pres-  Nom. Water
flow in gpm 
460/3/60 
h 
HP 
no 
flow 
sor 
pump conn.
Tower
City 
1 pump 
2 pumps 
 
pump pump pump  gpm 
d hp  hp 
in. 
NPT water 
ewater rated running rated running
20  21.0 20.0 19.6  50.4 2 
@ 10
5.0 
2.0” 
61.7 
31.5 43.9  34.7  47.0
37.8 
25  25.7 24.7 24.3  61.7 2 
@ 13
5.0 
2.0” 
75.9 
38.6 55.9  38.2  59.0
41.3 
30  31.8 30.8 30.4  76.2 2 
@ 15
5.0 
2.5” 
93.9 
47.6 60.1  45.3  63.2
48.4 
c  Based on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. Optional additional process 
pump hp reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power). 
d  Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump. 
e  Based on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum. 
f  Based on availability of 70ºF (21ºC) city water at 25 psi (172.4 kPa/1.7 bars) minimum. 
g  An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total 
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 
on page 16), and add it to the chiller rated or running amperage. 
h  Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages. 
 
20 hp, 25 hp, and 30 hp water-cooled chillers come standard with 4” (101 mm) swivel casters. 
 
 
Com- 
Process connections, in. NPT 
Dimensions 
Weights 
HP 
pressor  1 pump  2 Pump no pump, 1 pump, no
in inches 
c  
Dry 
d Ship. d Oper. d e
 hp 
to/from 
to/from 
no 
tank
tank, 
to/from 
height
width depth  lbs.  lbs. 
lbs. 
20 
2 @ 10  2” / 3”  2.5” / 3” 
2.0” 
2” / 3” 
45.3” 
34.0” 
100.7” 1,495 1,745 
2,161 
25 
2 @ 13  2” / 3”  2.5” / 3” 
2.0” 
2” / 3” 
45.3” 
34.0” 
100.7” 1,680 1,930 
2,346 
30 
2 @ 15  2” / 3”  2.5” / 3” 
2.0” 
2” / 3” 
45.3” 
34.0” 
100.7” 1,885 2,135 
2,551 
c  To convert to cm, multiply by 2.54. Add to height dimension based on mounting options. 
d  Weight is for standard chiller. Some optional features will increase weight. Multiply by 0.454 to calculate Kg
Operating weight is with a full 80-gallon (303 liter) reservoir tank of water.