2-40 HP Portable Chillers 
Chapter 7: Appendix 
60 of 70 
Evaporator Water Pressure Drop Tables 
Note: 
A recirculation pump is required for flows greater than the maximum or 
less than the minimum indicated. 
Note: 
Process flow less than or greater than the flow rates shown below requires 
a recirculation pump. 
 
Pressure drops in 
ΔP, psig and kPa 
2 HP 
3.5 HP 
5 HP 
7.5 HP 
Flow 
Δ P 
Flow 
Δ P 
Flow 
Δ P 
Flow 
Δ P 
gpm 
lpm 
psig 
kPa 
gpm 
lpm 
psig 
kPa 
gpm 
lpm 
psig 
kPa 
gpm 
lpm 
psig 
kPa 
4.06 
15.4 
3.5 
24.1 
8.03 
30.4 
4.0 
27.6 
10.0 
37.9 
1.5 
10.5 
12.0 
45.4 
2.3 
16.1 
6.01 
22.8 
7.0 
48.3 
10.00 
37.9 
6.5 
44.8 
12.0 
45.4 
2.2 
14.8 
16.0 
60.6 
2.9 
20.1 
8.02 
30.4 
11.5 
79.3 
12.00 
45.4 
10.0 
69. 
18.0 
68.1 
4.7 
32.1 
20.0 
75.7 
5.0 
34.5 
10.00 
37.9 
18.0 
124.1 
14.00 
53.0 
13.0 
89.6 
24.0 
90.8 
7.3 
50.2 
24.0 
90.8 
6.9 
47.4 
16.00 
60.6 
18.0 
124.1 
28.0  106.0 
9.6 
65.9 
 
 
 
33.0  124.9 
12.7 
87.8 
10 HP 
15 HP 
20 HP 
25 HP 
Flow 
Δ P 
Flow 
Δ P 
Flow 
Δ P 
Flow 
Δ P 
gpm 
lpm 
psig kPa gpm lpm 
psig 
kPa 
gpm 
lpm 
psig 
kPa 
gpm 
lpm 
psig 
kPa 
22.0 
83.3 
4.7 
32.6 
30.0 
113.6 
4.5 
31.3 
40.0 
151.4
4.0 
27.6 
55.0  208.2 
5.5 
37.9 
30.0  113.6 
8.28 
57.1 
40.0 
151.4 
7.5 
51.7 
45.0  170.3 
4.0 
27.6 
58.0  219.5 
5.8 
40.0 
38.0 
143.8  12.91 
89.0 
50.0 
189.3  12.4 
85.2 
50.0 
189.3
5.0 
34.5 
61.0  230.9 
6.0 
41.4 
46.0 
174.1  16.77  115.6 
60.0 
227.1 
17.8  122.8 
52.0  196.8 
6.0 
41.4 
70.0  264.9 
8.5 
58.6 
50.0 
189.3  20.00  137.9 
70.0 
264.9 
24.2  166.6 
55.0 
208.2
6.5 
44.8 
 
30 HP 
40 HP 
Flow 
Δ P 
Flow 
Δ P 
gpm 
lpm 
psig kPa gpm lpm 
psig 
kPa 
72.0 
272.5 
6.0 
41.1 
44.7 
169.2 
2.0 
13.8 
75.0  283.9 
6.5 
44.8 
58.5 
221.4 
3.4 
23.4 
80.0 
302.8 
8.0 
55.2 
70.9 
268.3 
4.9 
33.8 
85.0  321.7 
9.5 
65.5 
81.6 
308.8 
6.3 
43.5 
 
105.7  400.0 
10.3 
71.0 
Note: 
These pressure drop values are valid for single- and no-pump portable 
chillers. 
 
Calculating Chiller Nominal Flow and Pressure to Process 
•  Flow rate: Obtain the flow reading from the appropriate pump curve. 
•  Pressure: Obtain a corresponding pressure reading from the pump curve you selected, 
then subtract the one-pump pressure drop listed in the above table using the 
appropriate chiller hp and flow rate. 
•  For two-pump (Process/Recirc) chillers, do not subtract pressure drop from table above 
for process pump.